Setting The Unit's Analog Outputs - Honeywell IAQPoint2 Guide De Démarrage Rapide

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Setting the Unit's Analog Outputs

This menu lets you adjust each of the four analog outputs, minimum and
maximum (e.g. the 4 and the 20).
Access the menu and use the arrows to scroll to the SetAnOut. menu
and press enter to select.
The SetAnOut menu is displayed. In this menu, you can scroll to
select the output (from Min 1 to Min 4 and Max 1 to Max 4) and press
enter to select.
The AdjAnOut screen appears. Press on the up arrow to increase
the analog output value or the down arrow to decrease (the 301EM's
screen does not change or display any changes; the value will only be
visible on the connected meter).
When the desired output value is reached, press enter to confirm.
The screen displays *WAIT* while the unit is reinitialized.
The screen returns to the main menu.
Repeat these steps for each output to adjust.
Note that this menu does not display how the output is being
adjusted. The Output must be connected (to an ammeter or
to the DDC) for readings to be viewed.
301EM User Manual
Programming and Calibration
Setting the Unit's Analog Outputs
43