Eliminating Circuit Humidity
If during the operation of the machine there is evidence of humidity in
the refrigerant circuits, it is essential to drain the circuit completely of
refrigerant and eliminate the cause of the problem. To remove all the
humidity, the operator must dry out the circuit by evacuating it to 70 Pa,
and then proceed to recharge it with the gas charge indicated in the
plate located on the unit.

DISMANTLING THE UNIT

SAFEGUARD THE ENVIRONMENT
Dispose of the packaging materials in compliance with the national or local le-
gislation in force in your country. Do not leave the packaging within reach of
children.
It is advisable that the dismantling of the unit is performed by a company
authorised to collect obsolete products and machinery. The unit as a
whole is composed of materials considered as secondary raw materials
and the following conditions must be complied with:
the compressor oil must be removed, recovered and delivered to a
facility authorized to collect waste oil;
refrigerant gas may not be discharged into the atmosphere. It should in-
stead be recovered by means of homologated devices, stored in suita-
ble cylinders and delivered to a company authorised for the collection;
are considered special waste, and must be delivered to a body autho-
rized to collect such items;
the expanded polyurethane rubber insulation of the water exchanger
and the sound-absorbent sponge lining the bodywork must be removed
and processed as urban waste.