Connection To Flue Pipe; All Components Making Up The Chimney; Combustion Air Intake - Palazzetti SUNNY FIRE Manuel D'installation Et D'entretien

Masquer les pouces Voir aussi pour SUNNY FIRE:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

6.4

CONNECTION TO FLUE PIPE

Dimensioning the ue must be executed in accordance
with EN 13384-1.
It is advisable to make the connection for smoke outlet
between the replace and the ue pipe with curves and
metallic pipes of a suitable thickness, taking care not to
exceed and inclination of 45° (see Fig. 6.8:- A - curve,
B - ceramic bber rock wool insulation, C - short section)
if the ue pipe is not perpendicular to the ue pipe.
When the connection has been made, it is
to insulate the metallic pipes of the smoke outlet with rock
wool which may be externally covered with aluminium
foil.
• Do not use bre glass wool or insulation with a paper
base: they may catch re.
6.5
ALL COMPONENTS MAKING UP THE
CHIMNEY SYSTEM MUST BE DECLARED
AS BEING SUITABLE FOR THE SPECIFIC
OPERATING CONDITIONS AND CE
MARKED. AIR INTAKE CONNECTION
It is necessary to provide an external air intake to
The dimensions of the hole must comply with the values
set forth in the table of technical data shown in the
"Product booklet".
According to local standards in force, air intake could be
taken directly from the room or connected to the replace.
• Is forbidden the intake of air for combustion from
garages, rooms where ammable materials are stored
or where there is danger of re.
• The combustion air intake should be protected by
an anti-insect grille and placed where it can not be
accidentally obstructed, and made in such a way that
the useful cross-section allows the right amount of
oxygen to reach the replace.
In the room where the replace is located, if there are
one or more extraction fans (exhaust hoods and the like),
there may be problems with combustion due to lack of
combustion air.
For rooms greater than 25 m
room air recirculation grille (A) alongside the cladding
or use the wood compartment if there is one (G) (Fig.
6.9a).
6.5.1

Combustion air intake

Some models of Ecomonoblocco may be fitted (as
in the bottom compartment (P, Fig. 6.9b), for combustion
air connection to the outside air intake (C) via suitable
ductwork. For connections exceeding 1 m in length,
the diameter of the combustion air intake duct must be
increased.
advisable
it is advisable to provide a
2
max 45°
A
H=2D
D
C
A
C
A
B
C
- 6.8 -
G
- 6.9a -
P
G
- 6.9b -