Removing The Casing; Mounting The Est Fancoil - EURAPO ESTSV Série Manuel D'utilisation Et Installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6.3 REMOVING THE CASING

1
In order to carry out the installation or the maintenance of the fancoil it is necessary to
remove the casing. Remove the grilles by lifting the access door on the left-hand side of the
2
housing, sliding the grilles and removing them; when removing a grille, pay attention not to
break the little feet underneath. At the same way, remove all the other grilles.
3
MODELS ESTSV, ESTSH, ESTPV, ESTPH
After removing the grilles, remove the four fixing screws at the top of the unit (Fig. 4).
Rotate slightly the casing in order to free it from the lower retainers and move the casing
4
away (Fig. 4a).
MODELS ESTSV/AF, ESTSH/AF, ESTPV/AF, ESTPH/AF, ESTSVR
5
After removing the grilles, remove the four fixing screws at the top of the unit (Fig. 4).
Loosen the fixing screws on the frontal air intake panel and take it away, then remove the
fixing screws at the bottom of the casing (Fig. 4b). Take the casing away horizontally by
6
rotating it slightly.
The casing has to be reinstalled before powering the unit. Repeat the above
mentioned operations in the opposite sequence.
7
8
9
10
+
Fig. 4

6.4 MOUNTING THE EST FANCOIL

When mounting the fancoil on the wall or ceiling, use the mounting holes already present
in the unit. These holes are located at the sides of the back panel (see Enclosure 1/A, point
15, 1/B point 12 and 1/C point 17).
The positions and distances must be respected for correct installation and working of each
model; see Encl. 2 of this manual.
A minimum distance of at least 85 mm must be left between the unit and the floor (in
case of vertical installation), or between the unit and the wall (in case of horizontal installa-
28