5
Electrical installation
5.1
Mains connection
{
Danger!
Dangerous electrical voltage
The discharge current to earth (PE) is > 3.5 mA AC or 10 mA DC.
Possible consequences:
ƒ
Protective measures:
ƒ
5.1.1
Fuses and cable cross−sections
Type
E82MV302_4B
E82MV402_4B
E82MV552_4B
E82MV752_4B
E82MV302_4B230
E82MV402_4B230
E82MV552_4B230
E82MV752_4B230
1)
Universal−current sensitive earth−leakage circuit breaker
Observe all national and regional regulations!
EDK82MV752 DE/EN/FR 7.2
Death or severe injuries when touching the device in the event of an error.
Implement the measures required in EN 61800−5−1. Especially:
– Fixed installation
– PE connection must comply with standards (PE conductor diameter
³ 10 mm
2
(Cu) or PE conductor must be connected twice)
Mains
3/PE AC
320 ... 550 V;
45 ... 65 Hz
l
Electrical installation
Mains connection
Installation acc. to EN 60204−1
Fuse
Circuit breaker
M16 A
B16 A
M20 A
B20 A
M25 A
B25 A
M32 A
B32 A
M16 A
B16 A
M20 A
B20 A
M25 A
B25 A
M32 A
B32 A
5
35
8200mot409
1)
FI
L1, L2, L3, PE
2
[mm
]
³ 300 mA
2.5
4.0
4.0
6.0
³ 30 mA
2.5
4.0
4.0
6.0
91