Recommended operating modes for standard applications
The following table helps you to select the appropriate mode of operation for standard
applications:
Application
Single drives
With strongly alternating loads
With a high starting duty
With speed control (speed feedback)
With a high dynamic performance (e.g. positioning and infeed drives)
With a torque setpoint
With torque limitation (power control)
Three−phase reluctance motors
Three−phase sliding rotor motors
Three−phase AC motors with a fixedly assigned frequency−voltage
characteristic
Pump and fan drives with a square−law load characteristic
Group drives
(several motors connected to one controller)
Equal motors and equal loads
Different motors and/or alternating loads
C0014 = 2: linear V/f characteristic control
C0014 = 3: square−law V/f characteristic control
C0014 = 4: vector control
C0014 = 5: sensorless torque control
EDK82MV752 DE/EN/FR 7.2
Commissioning
Selection of the operating mode
l
Operating mode
Setting in C0014
recommended
alternatively
4
2
4
2
2
4
2
5
2
4
2
2
2
3
2 or 4
2
2
6
99