No.
Name
Lenze
à
C0088
Rated motor
current
C0089
Rated motor
frequency
à
C0090
Rated motor
voltage
à
Motor cos 
C0091
C0119
Configuration of
v
motor
temperature
monitoring (PTC
input) / earth
fault detection
C0140* Additive
0.00
frequency
setpoint
(NSET1−NADD)
C0148*
Identifying
s
motor data
EDK82MV752 DE/EN/FR 7.2
Selection
0.0
0.1 (A)
50
10
{1 Hz}
50
{1 V}
0.40
{0.1}
0
0
PTC input inactive
1
PTC input active,
TRIP effected
2
PTC input active,
warning effected
3
PTC input inactive
4
PTC input active,
TRIP effected
5
PTC input active,
warning effected
−650.00
{0.02 Hz}
0
0
Ready
1
Start identification
l
V/f rated frequency (C0015), slip
compensation (C0021) and motor
stator inductance (C0092) are
calculated and saved
l
The motor stator resistance (C0084) =
total resistance of the motor cable and
motor is measured and saved
l
Commissioning
Important controller codes
IMPORTANT
à
650.0
Device−dependent
0.0 ... 2.0 x rated output current of the
controller
960
à
500
230 V for 230 V controllers,
400 V for 400 V controllers
à
1.0
Device−dependent
l
Earth fault detection
Configure signal output in C0415
active
l
If several parameter sets are used,
monitoring has to be set
separately for every parameter set.
l
Deactivate earth fault detection if
the earth fault detection is
Earth fault detection
actuated unintentionally.
inactive
l
If the earth fault detection is
activated, the motor starts with a
delay of approx. 40 ms after
controller enable has been set.
Selection via j function of the
650.00
l
keypad or parameter channel
l
Acts additively on the main
setpoint
l
Value will be stored when
switching the mains or removing
the keypad
l
C0140 is only transferred during
parameter set transfer with GDC
(not with keypad)
Only when the motor is cold!
1. Inhibit controller, wait until drive
is at standstill
2. Enter the correct values from the
motor nameplate in C0087,
C0088, C0089, C0090, C0091
3. Set C0148 = 1, confirm with v
4. Enable controller:
The identification
– starts, c goes out
– the motor "whistles" faintly but
it does not rotate!
– takes approx. 30 s
– is completed when c is lit
again
5. Inhibit controller
6
111