Commissioning
Important controller codes
Code
Possible settings
No.
Name
Lenze
C0003*
Saving
v
parameters
non−volatilely
C0007
Fixed
v
configuration
digital inputs
uSEr
C0007
v
uSEr
(Contin.)
C0007
v
uSEr
(Contin.)
108
Selection
1
0
Do not save parameters in the EEPROM
1
Always save parameters in the EEPROM
3
Save your own basic setting in the EEPROM Afterwards save parameter set 1 as
0
E4
E3
0
CW/CCW
DCB
1
CW/CCW
PAR
CW/CCW
QSP
2
CW/CCW
PAR
3
CW/CCW
QSP
4
5
CW/CCW
DCB
6
CW/CCW
PAR
7
CW/CCW
PAR
8
CW/CCW
QSP
9
CW/CCW
QSP
10
CW/CCW
TRIP−Set
E4
E3
11
CW/CCW
DCB
12
CW/CCW
PAR
13
CW/CCW
QSP
CCW/QSP
CW/QSP
14
CCW/QSP
CW/QSP
15
16
CCW/QSP
CW/QSP
17
CCW/QSP
CW/QSP
18
CCW/QSP
CW/QSP
19
CCW/QSP
CW/QSP
E4
E3
20
CCW/QSP
CW/QSP
21
CCW/QSP
CW/QSP
22
CCW/QSP
CW/QSP
23
H/Re
CW/CCW
24
H/Re
PAR
H/Re
DCB
25
H/Re
JOG1/3
26
27
H/Re
TRIP−Set
28
JOG2/3
JOG1/3
29
JOG2/3
DCB
30
JOG2/3
QSP
l
IMPORTANT
Data loss after mains switch−off
l
Active after every mains
connection
l
Cyclic alteration of parameters via
bus module is not permissible
own basic setting with C0002 = 9
Change of C0007 is copied into the
corresponding subcode of C0410.
Free configuration in C0410 sets
C0007 = 255!
l
CW/CCW = clockwise
E2
E1
rotation/counter−clockwise
JOG2/3
JOG1/3
rotation
JOG2/3
JOG1/3
l
DCB = DC injection brake
JOG2/3
JOG1/3
l
QSP = quickstop
l
PAR = change over parameter set
DCB
JOG1/3
(PAR1 ó PAR2)
PAR
JOG1/3
– PAR1 = LOW, PAR2 = HIGH
TRIP−Set
JOG1/3
– The terminal in PAR1 and PAR2
TRIP−Set
JOG1/3
has to be assigned with the
"PAR" function.
DCB
TRIP−Set
– Only use configurations with
PAR
TRIP−Set
"PAR" if C0988 = 0
TRIP−Set
JOG1/3
l
TRIP−Set = external error
UP
DOWN
l
Selection of fixed
E2
E1
setpoints
UP
DOWN
JOG1/3
UP
DOWN
LOW LOW
UP
DOWN
HIGH LOW
DCB
JOG1/3
LOW HIGH
HIGH HIGH
PAR
JOG1/3
JOG2/3
JOG1/3
PAR
DCB
PAR
TRIP−Set
DCB
TRIP−Set
l
UP/DOWN = motor potentiometer
E2
E1
functions
TRIP−Set
JOG1/3
l
H/Re = manual/remote
UP
DOWN
change−over
UP
JOG1/3
l
PCTRL1−I−OFF = switch off I
component of process controller
UP
DOWN
l
DFIN1−ON = digital frequency
UP
DOWN
input 0 ... 10 kHz
UP
DOWN
l
PCTRL1−OFF = switch off process
UP
DOWN
controller
UP
DOWN
DFIN1−ON
PCTRL1−I−OFF
DFIN1−ON
PCTRL1−I−OFF
DFIN1−ON
PCTRL1−I−OFF
Active
JOG2/3
C0046
JOG1
JOG2
JOG3
EDK82MV752 DE/EN/FR 7.2