Commissioning of 8200 motec without function module
The 8200 motec can only be used when the FIF cover 0 is mounted! (delivery status).
l
– If the FIF cover is not mounted, the 8200 motec is inhibited (keypad: dc).
l
Since the 8200 motec without a function module does not provide any control termi-
nals, starting and stopping during operation is also possible by switching the mains.
The j function saves the setpoint at the time the operation is interrupted when swit-
l
ching the mains or in case of mains failures. The drive restarts automatically as soon as
the mains recovers!
If the drive does not start at step ƒ (c is not off), press U to enable the 8200 motec.
l
l
The 8200 motec (device variant with digital switching output K1) without function mo-
dule requires an external DC voltage for the operation of this output.
E82ZWLxxx
E82ZBB
a
e
b c d
8
P S
h
i
k
f
g
j

8 8
8 8
8
8 8
o
n
m
p
8
8 8
r
8 8
q
m
1
H i
A V
H z
° C
W
s h
%
L o
m
r p
z
x
w
y
8200mot170
Step

Connect diagnosis terminal (contains
keypad) with motec. Put the plug of
the connecting cable into the AIF in-
terface on the motec.
Connect mains voltage.
Automatic start is possible!
ƒ
Select setpoint via the j function.
Faults during commissioning or operation? ^ chapter 7
62
L1 / L2 / L3 / PE
2
d
c
j
0140
5000
z
w x
y
V
U
W
2
2
2
W
V
U
1
1
1
E
P
j
w
z
0....+50 Hz
y
0....- 50 Hz
Comment
Diagnosis terminal and connecting cable are not included in the scope of supply.
The controller is ready for operation after approx. 1 second.
Keypad: dc
Activate j
g w j
z
CW rotation
y
CCW rotation
l
3
Hz
c goes off. The drive is running now.
Display indicates output frequency.
A
8200mot146
EDK82MV752 DE/EN/FR 7.2