Commissioning
Important controller codes
Code
Possible settings
No.
Name
Lenze
C0014
Operating mode
v
C0015
V/f rated
50.00 7.50
frequency
uSEr
à
C0016
V
boost
min
uSEr
C0034*
Range of
v
setpoint
selection
uSEr
Standard I/O
(X3/8)
C0034*
Range of
v
setpoint
selection
(A)
Application I/O
uSEr
1 X3/1U, X3/1I
2 X3/2U, X3/2I
C0037
JOG1
20.00 −650.00
C0038
JOG2
30.00 −650.00
C0039
JOG3
40.00 −650.00
C0050*
Output
frequency
uSEr
(MCTRL1−NOUT)
à
C0087
Rated motor
speed
110
Selection
2
2
V/f characteristic control V ~ f
(linear characteristic with constant V
boost)
3
V/f characteristic control V ~ f
(square−law characteristic with constant
V
boost)
min
4
Vector control
5
Sensorless torque control with speed
limitation
l
Torque setpoint via C0412/6
l
Speed limitation via setpoint 1
(NSET1−N1) if C0412/1 is assigned,
otherwise via maximum frequency
(C0011)
{0.02 Hz}
0.00
{0.01 %}
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA
1
Current 4 ... 20 mA
2
Bipolar voltage −10 V ... +10 V
3
Current 4 ... 20 mA open−circuit monitored
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
1
Bipolar voltage −10 V ... +10 V
2
Current 0 ... 20 mA
3
Current 4 ... 20 mA
4
Current 4 ... 20 mA open−circuit monitored
{0.02 Hz}
{0.02 Hz}
{0.02 Hz}
−650.00
{Hz}
300
{1 rpm}
l
IMPORTANT
l
Commissioning is possible without
identifying motor parameters
min
l
Advantage of identification with
C0148:
– Improved smooth running at
low speeds
2
– V/f rated frequency (C0015) and
slip (C0021) are calculated and
saved. They do not have to be
entered
In the case of the first selection enter
the motor data and identify them
with C0148
Otherwise commissioning is not
possible
When C0014 = 5, C0019 must be set =
0 (automatic DC injection brake is
deactivated)
l
960.00
C0015 is calculated and saved
during the motor parameter
identification with C0148.
l
The setting applies to all
permitted mains voltages
à
40.00
device−dependent
Setting applies to all permitted mains
voltages
Observe switch position of the
function module!
Reversal of rotation direction only
possible with a digital signal.
l
Minimum output frequency
(C0010) not effective
l
Individually adjust offset and gain
TRIP Sd5 if I < 4 mA
Reversal of rotation direction only
possible with a digital signal.
Observe jumper position of the
function module!
Minimum output frequency (C0010)
not effective
Reversal of rotation direction only
possible with a digital signal.
Reversal of rotation direction only
possible with a digital signal.
TRIP Sd5 at I < 4 mA
650.00 JOG = fixed setpoint
Additional fixed setpoints ðC0440
650.00
650.00
650.00 Read only: Output frequency without
slip compensation
à
16000
Device−dependent