Electrical Installation; Installation According To Emc (Installation Of A Ce−Typical Drive System) - Lenze 9300 vector Instructions De Montage

Masquer les pouces Voir aussi pour 9300 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5

Electrical installation

Installation according to EMC (installation of a CE−typical drive system)
5
Electrical installation
(
Stop!
The drive controller contains electrostatically sensitive components.
The personnel must be free of electrostatic charge when carrying out assembly
and service operations.
5.1
Installation according to EMC (installation of a CE−typical drive system)
Always separate motor cables from mains cables and control cables.
ƒ
Cross the motor cable at right angles with mains cables and control cables.
ƒ
Ideally the motor cable should be installed without interruptions.
ƒ
Connect all components (controller, choke) to a central earthing point (PE rail).
ƒ
Always connect the shields to the mounting plate with a contact surface as large as
ƒ
possible or use the shield connections on the device side.
Always connect the motor cable shield to both sides − to the controller and to the
ƒ
motor.
The cables of the analog and digital inputs and outputs must be shielded. Short
ƒ
(up to 200 mm), unshielded cables must always be twisted.
The shield connections of the control cables must have a distance of at least 50 mm
ƒ
to the shield connections of the motor and DC cables.
Digital cables require a double−sided shield connection.
ƒ
Analog cables require a single−sided shield connection on the inverter side.
ƒ