Standard configuration of the single relays is as follows:
Rela
Alarms/Statuses
y
RL1
Alarm = AS1 NO NETWORK
Alarm = AS8 BACTERIA
RL2
DISCHARGING
RL3
Alarm = AS9 END AUT BATTERY
RL4
Alarm = AS10 BATTERY FAULT
NORMAL MODE
Alarm = AS16 BYP → LOAD
RL5
ECO MODE
Status = SS7 BYPASS → LOAD
RL6
Alarm = AS30 GENERAL ALARM
RL7
Alarm = AS6 BACTERIA IN TEST
RL8
Alarm = AS7 BCB OPEN
RL9
Alarm = AS13 INV OUT OF TOL
Alarm = AS14 WRONG BYPASS
RL10
CYCLIC DIRECTION
Relay output specifications:
Voltage 250 Vac
Voltage 30 Vdc
4.5.2.11 Terminal board X14 – RS485 Modbus
➢ X14-1 A-RS485-1;
➢ X14-1 A-RS485-1;
➢ X14-3 GND-RS485-1;
➢ X14-4 A-RS485-2;
➢ X14-5 B-RS485-2;
➢ X14-6 GND-RS485-2;
The number of contacts can vary based on the system and depends on the purchase
options.
Installation and start-up of KEOR XPE UPS
Installation et démarrage de l'ASI KEOR XPE
Installazione e avviamento KEOR XPE UPS
Not energ. if
alarm present
Not energ. if
alarm present
Not energ. if
alarm present
Not energ. if
alarm present
Not energ. if
alarm present
Energised if
status is present
Not energ. if
alarm present
Not energ. if
alarm present
Not energ. if
alarm present
Not energ. if
alarm present
Not energ. if
alarm present
Current 1A
Current 1A Resistive load
Status
Pin
functioning
X13
2-3
1-2
5-6
4-5
8-9
7-8
11-12
10-11
13-14
14-15
14-15
13-14
17-18
16-17
20-21
19-20
23-24
22-23
26-27
25-26
29-30
28-29
M1
Led (in SRC board)
Normal
Name
status
Closed
SRC1-
DL1
Open
Closed
SRC1-
DL2
Open
Closed
SRC1-
DL3
Open
Closed
SRC1-
DL4
Open
Closed
Open
SRC1-
DL5
Closed
Open
Closed
SRC2-
DL1
Open
Closed
SRC2-
DL2
Open
Closed
SRC2-
DL3
Open
Closed
SRC2-
DL4
Open
Closed
SRC2-
DL5
Open
OMAF9212 REV. A
Normal
functioning
status
On
On
On
On
On
On
On
On
On
On
59