Alarm
AS30
Description
Common alarm
or
At least one Power Unit has enabled alarm A30 COMMON ALARM.
➢ At least one alarm is present.
Possible
causes
➢ Refer to alarm A30 COMMON ALARM of the Power Unit.
Solutions
1. Check which alarms are present and follow the indicated
procedures.
2. Refer to alarm A30 COMMON ALARM of the Power Unit.
Alarm
AS31
Description
The bypass isolator is open.
➢ The input bypass isolator is open.
Possible
causes
Solutions
1. Check the status of the input isolator switch.
2. Check the functionality of the auxiliary contact of the isolator.
3. If the alarm persists, contact our technical support service.
Alarm
AS32
Description
The output switch of the system is open.
➢ Output isolator of the system open.
Possible
causes
Solutions
1. Check the status of the system output switch.
2. Check the functionality of the auxiliary contact of the isolator.
3. If the alarm persists, contact our technical support service.
Alarm
AS33
Description
At least one Power Unit has enabled alarm
A33 ASYMMETRIC LOAD.
➢ Refer to alarm A33 ASYMMETRIC LOAD of the Power Unit.
Possible
causes
Solutions
1. Refer to alarm A33 ASYMMETRIC LOAD of the Power Unit.
Alarm
AS34
Description
At least one Power Unit has enabled alarm A34 SERVICE REQUIRED.
➢ Refer to alarm A34 SERVICE REQUIRED of the Power Unit.
Possible
causes
Solutions
1. Refer to alarm A34 SERVICE REQUIRED of the Power Unit.
KEOR XPE UPS user manual
Utilizzo dell'UPS KEOR XPE
COMMON ALARM
SBCBS OPEN
OCBS OPEN
ASYMMETRIC LOAD
SERVICE REQUIRED