Installation et démarrage de l'ASI KEOR XPE
Figure 28 - Start screen for 4 Power Units.
4)
Having terminated the start phase of all the Power Units, you automatically go to the
final part of the start sequence. You can also start the system not completely leaving
some Power Units off. When the condition occurs for the system to go forward despite
the system not being completely started, a SKIP key appears. Pressing it, the operator
can continue the start sequence.
Figure 29 - Start screen terminated for 3 Power Units of 4
Installation and start-up of KEOR XPE UPS
Installazione e avviamento KEOR XPE UPS
OMAF9212 REV. A
67