Burkert 8400 Manuel Utilisateur page 60

Masquer les pouces Voir aussi pour 8400:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

The tightness of the device is not guaranteed when the EN
175301-803 fixed connector is not wired:
unscrew the nut [1] (see
connector provided with the device;
insert the plug provided with the 2508 connector into
the cable gland;
tighten the nut;
insert the plugged 2508 connector into the
EN 175301-803 fixed connector.
Not connected
0 VDC
3
4
(*)
5
2
1
V+ (12 - 30 VDC)
Not connected
Fig. 14:
Assignment of the pins on the M12, 5-pin fixed connector
on a version with relay output
18
Fig. 7) on the 2508 female
(*) Functional earth
english
Type 8400
Installationandwiring
1
Common
3
Normally Open
Fig. 15:
Assignment of the pins on the EN 175301-803 fixed con-
nector (connecting the relay output)
pin for the m12 female cable available as
optional equipment (order code 438680)
1
2
3
4
5
The M12, 5-pin fixed connector is adjustable:
Unscrew the locknut.
Turn the fixed connector to the desired position, by 360° max. so
as not to twist the cables inside the housing.
Tighten the locknut using a spanner, while keeping the fixed con-
nector in the desired position.
Not connected
Normally Closed
2
colour of the
conductor
brown
white
blue
black
grey

Publicité

Table des Matières
loading