11 Technical data

Table 76:
Technical data
General data
Dimensions (width x height x depth)
Weight
Operating temperature range
Storage temperature range
Ambient operating conditions
Vibration resistance
Shock resistance
If the unit has more than three I/O modules, retaining brackets must be used. The maximum
permissible space between the retaining brackets is 150 mm.
Protection class according to
EN60529/IEC529
Relative humidity
Degree of contamination
Use
Electronics
Power supply
Sensor voltage (from UL of bus
module)
(input module)
Max. cable length
Functional earth (FE)
Input module 2AI2M12-E
Connections
Input resistance
Maximum input voltage
Proximity switching rate
Input precision (over the full range)
Analog inputs
(voltage or current):
50 mm x 34 mm x 82 mm
0.11 kg
-10°C to 60°C
-25°C to 80°C
Max. height above sea level: 2000 m
Wall mounting EN 60068-2-6:
±0.35 mm displacement at 10 Hz–60 Hz,
5 g acceleration at 60 Hz to 150 Hz
Wall mounting EN 60068-2-27:
30 g with 18 ms duration,
3 shocks each direction
IP65 with assembled connections
IP20 with open connections
95%, non condensing
2
Only in closed rooms
By the bus coupler via the backplane
24 V DC ±25%
The total current for all sensor supplies on an input module must not
exceed 0.5 A.
30 m
Connection according to DIN EN 60204-1
Input connection X2N1–X2N2:
Socket, female, M12x1, 5-pin, A-coded
Voltage measurement range: approx. 100 kΩ
Current measurement range: approx. 120 Ω
Voltage measurement range: ±12 V
Current measurement range: ±5 V
1 ms for all 2 channels
Total error: ±0.2%
Linearity: ±0.05%
Temperature drift: ±2 ppm/°C