3.3.2. Installing the restrictor plate

The restrictor plate is installed at the top inside the combustion chamber of the unit
and serves to adapt the draught in the unit to the pipe path that has been worked
out.
The restrictor plate can be installed in 4 positions, indicated with 0, 1, 2 and 3, as
shown in the figure below.
When the unit is delivered the plate is installed in position 0. If a different position
is required, the plate simply has to be unscrewed and reinstalled in the position re-
quired.
position 0

3.3.3. Installation with horizontal (wall) terminal

General directions
Ducts and vent sleeves must be at least 50 mm away from combustible material,
everywhere.
All elements of both the air intake and flue gas exhaust systems must be in-
serted into each other to a minimum of 30 mm and be secured by the use of
clamps, USKB 10, or stainless steel screws.
For outlets in the vicinity of a property line or ventilation openings you are re-
ferred to the applicable national and regional codes.
Choice of the outlet area
The flue gas outlet can reach a temperature of 200 °C. Therefore, it is important
to choose the outlet area with care in order to prevent any person from possibly
coming into contact with the flue gas outlet.
The temperature of the flue gasses themselves from this type of unit can run as
high as ca. 400 °C Outlets beneath overhangs and awnings can be dangerous
due to the accumulation of hot combustion gasses and are therefore not permit-
ted.
2000DV - 2080DV
position 1
Positions of the restrictor plate
44
position 2
position 3
03.27987.000