Summary Of The Conditions For Sending The Upstream Frames; Downlink Frames; Device Configuration Request Frame; Network Configuration Request Frame - ADEUNIS ARF8283A Guide Utilisateur

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

LoRaWAN DELTA P - Guide utilisateur / User guide version V1.0.0
4.1.14

Summary of the conditions for sending the upstream frames

The table below summarizes the conditions for sending the various uplink frames:
Code
0x10
Information frames on device configuration
FR
0x11
Information frames on product configuration
0x1F
Information frame on configuration of Digital Input(s)
EN
0x20
Information frames on Network configuration
0x30
Keep Alive frame
0x31
Reply frame to a register value request
0x33
Response frame following an update of register(s)
0x53
Frame of periodic readings (Pressure Delta)
0x54
Pressure delta alarm frame
0x55
Frame of periodic readings (analog input 0-10 V)
0x56
Alarm frame for analog input 0-10 V
0x51
Digital Input/output
0x52
Terminal alarm frame (Digital Input/output 2)

4.2. Downlink frames

LoRaWAN technology makes it possible to transmit information to the device from the network (downlink frame).
The class A of the LoRaWAN specification allows the device to receive information from the network by proposing two listening windows after
each uplink communication (uplink frame).

4.2.1 Device configuration request frame

This frame allows you to inform the device through the network that it must resend the device configuration uplink frame (0x10 and 0x11).
0
Code
0x01

4.2.2 Network configuration request frame

This frame allows you to inform the device through the network that it must resend the network configuration uplink frame (0x20).
0
Code
0x02
Description
1
2
X
X
1
2
X
X
Device start up
Exit configuration mode
Receiving a 0x01 downlink
Starting the product
Exit configuration mode
Receiving a 0x01 downlink
Device start up
Exit configuration mode
Device start up
Exit configuration mode
Receiving a 0x02 downlink
Periodically in pure event mode
Receiving a 0x40 downlink
Receiving a 0x41 downlink
According to defined period
Exceeding a threshold
According to defined period
Exceeding a threshold
By default, at each event
Exceeding a threshold if configured
By default, at each event
Exceeding a threshold if configured
3
4
PAYLOAD
X
X
3
4
PAYLOAD
X
X
Sending conditions
5
6
X
X
5
6
X
X
7
X
7
X
Page
80
of 88

Publicité

Table des Matières
loading

Table des Matières