LoRaWAN DELTA P - Guide utilisateur / User guide version V1.0.0

3.2.3 AT Command

A command starts with the 2 ASCII characters: «AT», followed by one or more characters and data (see the list below for the syntax of the AT
commands available on the modem).
Each command must end with a "CR" or "CR" "LF", both are acceptable. (CR indicates: Carriage Return, LF indicates: Line Feed).
Once the command has been received, the modem returns:
• Data" <cr> <lf>, for ATS type playback control <n>? AT/S or AT/V.
FR
• O" <cr> <lf>, for all other commands when this has been accepted.
• "E" <cr> <lf>, if it refuses the command due to a syntax error, unknown command, unknown register, invalid parameter, ....
• "CM" <cr> <lf>, if it accepts the input in command mode
AT Command Table:
EN
Command
+++
ATPIN <PIN>
AT/V
AT/N
AT/ARF
ATS<n>?
AT/S
ATS<n>=<m>
ATR APP
AT&W
ATO
ATT63 PROVIDER
Description
Input request in command mode
Gives access to AT commands if register S304 is not
0
Displays the firmware version of the application and
the firmware version of the RTU module
Displays the network used
Displays the device reference
Returns the contents of the <n> register
Displays all registers
Sets <m> to the registry <n>
Resets the default configurations of the application
part
Saves the new configuration
Exits command mode
Provider password
Reply example
«CM»<cr><lf>
APPx_Vxx.xx.xx:RTUx_Vyy.yy.yy
"LoRa" or "SIGFOX" or «WMBUS»
«ARF8240CAA\r\n»
S<n>=<y><cr><lf> avec <y> as a registry content
/
«O»<cr><lf> si ok, «E»<cr><lf> si erreur, «W»<cr><lf>
if consistency error
«O»<cr><lf>
«O»<cr><lf>, «E»<cr><lf> if consistency error
«O»<cr><lf>, «E»<cr><lf> if consistency error
«O»<cr><lf>