LoRaWAN DELTA P - Guide utilisateur / User guide version V1.0.0

2.1.5 Three transmission modes to meet needs

The device can mesures a delta pressure, save this information and send it in three transmission modes.
Periodic transmission allows data to
FR
be collected in a specified period of
Definition
time,
to be saved and sent on a regular
basis for analysis over time.
I want to take a reading of my
EN
pressure delta every half hour. I want
to minimize my number of uplinks to
Specific user
optimize my autonomy, so I want to
situation
put as many readings as possible in
each data frame without losing any
data.
Acquisition period
900 (900s x2 = 1800 seconds or 30
minutes)
Number of acquisitions
before backup
kup at each reading)
Number of backup before
Related confi-
transmission
guration
backups per frame)
• Pressure Delta alarm (S330) = 0
(alarm off)
• Input alarm 0-10 V (S350) = 0
(alarm off)
In the use
Paragraph 2.1.5.01
CAUTION: The ability to transmit information will depend on the network used. Here, the mentionned cases works with LoRaWAN technology.
The complete list of registers can be found in section 3.4.
Period of transmission = number of backups
Period of
acquisition
S321 = 10min
Reading
Log backup
Periodic transmission
(S321) =
(S320) = 1 (1bac-
(S301) = 24 (24
(logs) between each transmission
S301 = 12 X 1 hour = 12 hours
Transmission over threshold
The transmission of a frame over
threshold makes it possible to read data
according to a given period and to send
an alarm only if one of the thresh-
olds is exceeded.
I want the product to alert me if my pres-
sure delta falls below 100 Pa.
Acquisition period
(S321) =
300 (300s x2 =10 minutes)
Number of backups before
transmission
(S301) = 0 (no sending at
intervals)
• Type of delta pressure alarm
(S330) = 1 (low threshold)
• Lower threshold (333) = 100 (in Pa)
• Low threshold hysteresis
(S334) = 10 (in Pa) the alarm is triggered
only when pressure delta exceeds 110 Pa.
Paragraph 2.1.5.02
Backup period = number of readings
Sending
Periodic transmission and over
threshold
Mix of the two modes in order to be
able to read regularly to receive alerts
if the threshold is exceeded and to save
the information regularly to make the
analysis over time.
I want to know the pressure delta of
my VMC during the day and be alerted
if the pressure delta falls below 100
Pa. My product will send me an hourly
reading of the pressure delta twice per
day and trigger an alarm if my pressure
delta falls below 100 Pa.
Acquisition period
300 (300s x2 =10 minutes)
Number of acquisitions before
backup
(S320) = 6 (6 x 10 min = 1h)
Number of backups before
transmission
(S301) = 12 (12 X 1h
= 12h)
• Type of delta pressure alarm (S330) =
1 (low threshold)
• Lower threshold (333) = 100 (in Pa)
• Low threshold hysteresis
(S334) = 10 (in Pa) the alarm is trigge-
red only when pressure delta exceeds
110 Pa.
See schema below
between each backup
S320 = 6 x 10min = 1 hour
(S321) =
Time
Page
58
of 88