Sigfox DELTA P - Guide utilisateur / User guide version V2.0.1

2. DEVICE OPERATION

2.1. Operating modes

IMPORTANT NOTE: adeunis uses the Big-Endian data format
The device has several operating modes

COMMAND MODE

2.1.1 PARK MODE

The device is delivered in PARK mode, it is thus in standby mode and its consumption is minimal. Exit PARK mode by putting the magnet on
the "2" mentioned on the product for more than 5 seconds. The green LED lights up to indicate the detection of the magnet and then flashes
rapidly during the device start-up phase.
The device then sends its configuration and data frames.
2.1.2 COMMAND MODE
This mode is used to configure the device registers. There are two ways to enter this mode:
- Open the adeunis IoT Configurator application, connect a cable to the device's micro-USB port and connect it to the computer or mobile
phone.
- Connect a cable to the micro-USB port of the device and enter command mode via an AT command.
The output of the COMMAND mode is via the ATO command or the USB cable disconnection. The device will then return to its previous mode,
i.e. PARK or OPERATING.

2.1.3 OPERATING MODE

This mode allows the device to work in its intended end use.

2.1.4 Management of the battery low

When the product detects that the battery is not anymore in capacity to deliver the energy needed to send a frame (extreme temperatures or
end-of-life of the battery) it waits to be in capacity to transmit. If it detects that the delay generated is longer than 1 minute it informs the user
via the "battery low" flag in the status byte of each frame.
Product should
send a frame
The battery low alarm is switching off if the battery is replaced or when the temperature conditions are favorable for the proper functioning of
the battery.
Command send-
ing by serial link
Auto adaptation (cf
management of the
low battery)
yes
Battery is
The product is
no
sufficient
waiting to be
to send the
able to emit
frame
?
PARK MODE
Presence of a magnet
on the product >5s
OPERATION MODE
Send "battery
low" flag
OFF
(dead battery)
yes
Delay
no
no
is lower than 1
minute ?
Battery exchange
"Low battery"
no
The product
alarm appears in
sends its frame
status byte