1.3.2

- Connecting on motherboard

1.3.2.1 - Remote indication, remote control and station alarm port
("LOOPS")
"LOOPS" Interface:
Ports
Connector
Pin N°
1
9
2
10
3
11
4
12
5
13
6
14
7
15
8
NOTE:
OB is the result of a logical "OR" between signals OB1 and OB2 on the "PWR", "PWRA" and "PWRB"
power supply interfaces.
1.3.2.2 - Management and Administration ports
"COMM" Interface:
Ports
Bit rate
Connector
4 remote indication inputs for floating contacts (Local user inputs),
biased to -48 V internally, active when closed and with electrical
isolation (loop current = from 1 to 10 mA),
2 dry loop outputs (common, normally closed and normally open)
(Local user outputs) for station alarm or remote control use
(maximum current = 100 mA on resistive load),
Female 15-way HE5
8
15
Signal name
BREAK B
COMMON B
MAKE B
Break A
COMMON A
Make A
GND
R- MON 4 P (OB)
R-MON 4 N
R- MON 3 P (OB)
R- MON 3 N
R- MON 2 P (OB)
R- MON 2 N
R- MON 1 P (OB)
R- MON 1 N
RS232, connecting VT100 standard console or emulation
19200 bauds (8 data bits, no parity bit and 1 stop bit),
Female 9-way HE5
No reproduction or communication without the written consent of SAGEM SA
1 - INSTALLATION AND COMMISSIONING
1
9
Comments
Normally closed contact of dry loop B
Common contact of dry loop B
Normally open contact of dry loop B
Normally closed contact of dry loop A
Common contact of dry loop A
Normally open contact of dry loop A
Ground
User imput N°4
User imput N°3
User imput N°2
User imput N°1
5
1
9
6
Installation and User Guide - N56717020104