Preparation for installing the unit
The surrounding atmosphere must be clean and at temperatures above 40 ºC, the relative humidity must be between
4% and 50%. Higher percentages of relative humidity up to 95% are tolerated at temperatures below 30 ºC.
It should be borne in mind that moderate condensation may occasionally occur as a consequence of temperature
variations. For this reason, apart from the unit's own protection, it is necessary to monitor these units once they
have been started up on sites where the conditions described above are not expected to be present.
In the event of condensation, never apply voltage to the unit.

5.3. Supporting Surface and Fastening

To guarantee good heat evacuation and promote sealing, the units must be placed on a perfectly vertical wall or,
failing this, with a slight slope of a maximum of +80° or -80°.
Reserve a solid wall to which to attach the unit. It must be possible to drill the wall and fit suitable wall anchors
and self-tapping screws to support the unit's weight.

5.4. Protection of the connection to the consumption grid

Thermomagnetic circuit breaker
A thermomagnetic circuit breaker must be installed on the connection between the inverter and the consumption
grid.
The following gable provides the necessary data for the installer to select said device according to the type of
installation (connected to the distribution grid or off-grid).
Installations with the inverter connected to the distribution grid
INGECON SUN STORAGE 1PLAY
3TL
6TL
Installations with the inverter disconnected to the distribution grid
INGECON SUN STORAGE 1PLAY
3TL
6TL
You must take into account when selecting the protection that the ambient working temperature influences the
maximum current permitted by these protections as indicated by the manufacturer.
ABH2013IQM01_C - Installation and Operation Manual
Maximum current
for the consumption grid
thermomagnetic circuit breaker
50 Arms
50 Arms
Maximum current
for the consumption grid
thermomagnetic circuit breaker
13 Arms
26 Arms
Rated current for the
63 Arms
63 Arms
Rated current for the
20 Arms
32 Arms
Ingeteam
EN
ES
FR
PT
19