Technical Data - ASO Safety Solutions ELMON relay 32-242 Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Safety Relay

12. Technical Data

Supply voltage
Low voltage:
Input power:
Ensuring low
voltage (external):
Terminal resistance oft the sensor
nominal value
upper switching point R
lower switching point R
Safety relay
Nominal current DC
Nominal current AC
Mechanical life-ti me
Saft ey Relay
Fuse type
Safety relay switching ti mes
Switching off delay
(response ti me)
Turn-off ti me
Assembly
Housing
Dimensions (HxWxD)
Housing
Housing incl. plug-in socket
Protecti on class
Weight
Temperature range
Connecti on terminals
ti ghtening torque
Connecti on cable cross-secti on
Certi fi cati ons
Electronics
Electromechanics
All voltages connected to the switching unit must be safely isolated!
*Not included in the scope of delivery
20
U
24 V AC/DC ±10 %
E
I
85 mA
E
I
180mA (100ms)
max
P
3 W 24 V DC
E-max
P
3 VA 24 V AC
E-max
125mA Medium acti ng fuse
125mA Flink can be used
alternati vely
R
8,2 kΩ
nom
> 12,0 kΩ
AO
< 5,0 kΩ
AU
DC-13 / 24 V / 2 A
AC-15 / 30 V / 2 A
>10
actuati ons
6
M 2 A 5 x 20 glass tube*
< 12 ms
500 ms (ELMON relay 32-242)
100 ms (ELMON relay 32-242 K)
(Power on 700ms)
Plug-in socket to 35 mm DIN snap-on rail
11 pol. DIN plug-in socket housing
with plug-in socket for 35 mm assembly rail
82 x 38 x 84 mm
82 x 38 x 110 mm
IP20
225 g
-25°C to +55°C
0,5 Nm
single- or fi ne-stranded cable 0,75-1,5 mm
EN ISO 13849-1:2015
Categorie 3 PL e
MTTFd 180 years, DC 90%
MTTFd 3757 years, DC 90 %
B10d 1000000 / MTTFd 190 years (Nop 52560)
2