Safety relay ISK 74-31
8.3

Commissioning / Functional test

The gate system must be tested for correct functioning once all of the electrical components have
been connected and the supply voltage has been turned on. To do so, activate each of the safety
contact edges one after another and check the relevant response of the switching device.
LED
Colour
Power
Green
Transmit
Red
Opening
Stationary
Red
Opening
Transmit
Red
Closing
Stationary
Red
Closing
The safety system must be professionally inspected at least once a year.
The inspection must be documented in such a way as to be reproducible. The requirements of
EN 12453 and EN 12445 must be taken into consideration and complied with.
26
Signals
Indicates
Supply voltage
Fault Opening movement
moving contact edge(s)
Fault Opening movement
stationary contact edge(s)
Fault Closing movement
moving contact edge(s)
Fault Closing movement
stationary contact edge(s)