Salicru SLC CUBE 3+ PS Mode D'emploi page 152

Publicité

Les langues disponibles

Les langues disponibles

Nominal power (kVA)
Nominal power (kW)
Output nominal voltage
Output power factor
Accuracy
Output frequency
Maximum slew rate
Output wave shape
Total output voltage harmonic distortion
Phase shifting
Dynamic response time
Permissible overload
(7)
Permissible crest factor
Permissible power factor
Unbalanced output voltage (100 % unbalanced load)
Current limit
Efficiency on battery mode (100% linear load) (%)
Type
Bypass line
Nominal voltage
Voltage range
Voltage hysteresis
Frequency
Frequency range
Frequency hysteresis
Activation criteria
Permissible overload
Transference to bypass
Re-transference
Static bypass for Peak Shaving
Type
Nominal voltage
Frequency
SHORT CIRCUIT CURRENT (kA)
Total efficiency (100% linear load) (%)
Quantity
Type
(8)
Floating voltage per battery
Compensation of the battery floating voltage
Capacity (Ah)
Standard charging current (Cx0,2) (A)
Battery terminal torque
Fitted in the same UPS cabinet
Peak Shaving functionality
Quantity of cabinets
CUBE3+ / CUBE3+ B1
Maximum
dimensions(mm)
CUBE3+ B / CUBE3+ B B1
(Depth x Width x Height)
Batteries
Casters without brake. Equipment / batteries
CUBE3+ B1
CUBE3+ B B1
Cabinet weight (kg)
CUBE3+
CUBE3+ B
External batteries
Tab. 9. Technical specifications of equipments with (HV) voltage.
152
7.5
10
Depending on the input/output setting and power supply voltage (See chart 9)
125 % for 10 min., >125.. 135 % for 5 min., >135.. 150 % for 1 min., > 150 % for 20 ms.
3.4 to 1
High overload, short-circuit: RMS voltage limit. High current crest factor: Peak voltage limit
94.3
94.8
Preset +12 % (adjustable between +20... +5%) / –15% (adjustable between –25... –5%
±2 % as regards to bypass voltage range. In a standard equipment is of +10 /–13%
1 Hz as regards the frequency range (selectable among 0.2 - 0.5 - 1.0 and 2.0 Hz)
MANUAL BYPASS (maintenance)
91.0
4.5
0.9
Dimensions AND WEIGHTS FOR UPS CONFIGURATIONS WITH STANDARD BACK UP TIME
1 (UPS + batteries)
97
97
99
99
207
207
209
209
-
-
15
20
30
40
50
INVERTER
Single phase 220V, 230V or 240V
Three phase 3x380V, 3x400V or 3x415V (4 wires: 3 phases + N)
0.9 for three phase/three phase setting and 0.8 for L, M, N or AUTO settings
Static: ±1 %. Dynamic: ±2 % (step loads 100-0-100 %)
50 / 60 Hz synchronised ±5 Hz. Free running ±0.05 %
From 1 to 10 Hz/s (programmable)
Sinewave
Linear load: THD-v < 0.5 %. Ref. non-linear load (EN-62040-3): THD-v < 1.5 %
120 ±1º (balanced load). 120 ±2º (unbalanced load of 100 % )
10 ms. at 98 % of the static value
3.2 to 1
0.7 leading to 0.7 lagging
< 1 %
95.3
95.6
95.9
96.4
96.3
STATIC BYPASS
Solid state
Common. Separate as an option (B)
Single phase 220V, 230V or 240V
Three phase 3x380V, 3x400V or 3x415V (4 wires: 3 phases + N)
50 / 60 Hz
±5 Hz (selectable among 0.5 - 1.0 - 2 and 5.0 Hz)
Controlled by microprocessor
400 % for 10 s
Immediate, for overloads higher than 150 %
Automatic after alarm cancelling
Configurable by user its possible activation
Make before break
Single phase 220V, 230V or 240V
Three phase 3x380V, 3x400V or 3x415V (4 wires: 3 phases + N)
50 / 60 Hz
6
GENERAL
92
92.5
93.5
94.0
BATTERIES
31 + 31
Pb-Ca
13.65 V at 20ºC
Adjustable (Preset to –18 mV/ºC)
7
9
12
12
1.4
1.8
2.4
2.4
According to battery manufacturer
YES
Dimensioning for energy storage and provide load demand peaks
775x450x1100
-
YES / -
YES / YES
99
102
147
172
-
101
105
150
175
-
209
235
319
417
185
211
237
322
420
190
-
-
-
-
321
60
80
100
120
-
2.8 to 1
3.2 to 1
96.4
96.4
96.5
96.4
96.8
-
-
10
25
100
95.0
94.5
94.0
2x12
40
4.8
8.0
NO
1 (UPS) / 1 (batteries)
880x590x1325
850x900x1905
880x870x1325
850x1225x1905
1050x650x1325
850x1305x1905
YES / NO
-
-
-
-
-
-
-
-
185
265
290
290
190
275
310
310
551
1020
1020
1020
1655
160
200
3 to 1
96.9
95.0
65
80
13
16
NO / NO
-
-
-
-
540
550
570
580
1690
SALICRU