Lapsed this period of time, connect the equipment to mains
together with the battery set if any, paying attention to the
safety instructions and connection.
Models with separate static bypass line, is not needed to
ˆ
connect this power terminal strip.
ˆ Proceed to start it up as it is described in section 6, do
not turn «On» the output switch (Q2), and do not start
up the inverter through the control panel (PC).
Leave the equipment in this mode for 12 hours as minimum.
ˆ Once the battery recharging is finished, proceed to
shutdown the equipment, disconnect it electrically and
store the UPS and batteries if any, inside their original
packaging, by writing down the new data of battery
recharge into the label box (see Fig. 29).
ˆ Regarding the battery recharge, units that belong to a
parallel system will be treated as single equipments, so
it is not needed any additional connection.
Do not store the equipments and/or battery modules, in places
where either temperatures exceed over the stated ones in the
technical specifications of section «9. Annexes» or indications in
section «2.2.3.3. Safety warning regarding batteries» are not re-
spected.
5.1.3. Transport until its location.
UPSs up to 60 kVA (LV) / 120 kVA (HV) have casters, in order to
make easier their transport until their location, where the two
front casters are swivel and the rear ones are fix.
In the same way the battery cabinet has casters with identical
structure, but in the smallest size of battery cabinet only.
For the rest of the models will be needed the use of a pallet
jack or fork lift.
In any case pay attention to the weights stated in section «9.
Annexes», in order to use the suitable mediums of transport
for the weight of the equipment (pallet jack, fork lift, service
lift or lift,... ), as well as the features of the location (type of
floor, resistance of the floor kg/m
5.1.4. Location, immobilised and considerations.
5.1.4.1. Location for single equipments.
As an example, Fig. 30 shows typical cases depending on the
model. The one that is made up of a single cabinet, the one for
B
UPS cabinet
with
batteries
A
D
A
Fig. 31. Minimum peripheral dimension lines for UPS cooling.
114
,.. ).
2
B
UPS
UPS battery
cabinet
cabinet
A
D
A
A
the UPS with the batteries inside, the one for the UPS with the
batteries in an independent cabinet or extended back up time.
For cooling the unit it is necessary to leave its contour free
ˆ
of obstacles. Respect the minimum distances indicated in
the table in section 1.2.1 of document EK266*08 (Safety
instructions), which indicates the values for dimensions A,
B, C and D according to the power of each equipment.
For the battery cabinets, keep the same distances as for
the UPS itself that configures the system.
It is recommended to leave an additional 75 cm free on
ˆ
the sides, for possible interventions by the (S.S.T.) or the
necessary slack in the connection cables to facilitate
forward movement of the equipment.
For extended back up time with more than one cabinet, it is
recommended to place one on each side of the equipment and,
in the event of a greater number of battery cabinets, repeat the
same sequence alternately.
5.1.4.2. Location for parallel systems.
As i.e. Fig. 31 shows 4 equipments in parallel with their respec-
tive battery cabinet. For systems with less units act in each
case accordingly.
It is advisable to put them in order by the Nr stated in the door
of each equipment. The number corresponds to the assigned
address preset from factory.
The arrangement is not random, because the length of battery
wires (3,5 m.) and communication BUS (5 m.), this is the best
one. For a higher quantity of battery cabinets in systems with
extended back up time, follow the same criteria keeping the
symmetry.
When the system is structured by models with batteries and
power electronics in the same cabinet, forget the battery mod-
ules illustrations.
ˆ In order to have a correct cooling of the equipment,
leave the surrounding space free of obstacles. Respect
the minimum distances stated in the table of section
1.2.1 from EK266*08 (Safety instructions), where the
figures, depending on the power rate of each equip-
ment, for the A, B, C and D dimension lines are stated.
For battery cabinets, keep the same distances as for the
UPS that makes the system.
UPS
cabinet
A
A
B
UPS battery
UPS battery
cabinet
cabinet
nr 1
nr 2
D
A
A
SALICRU