Télécharger Imprimer la page

Salicru SLC CUBE 3+ PS Mode D'emploi page 141

Publicité

Les langues disponibles

Les langues disponibles

Displayed measurements in screens 2.1 to 2.8, 2.20,
2.28 and 2.29 will be according to the input and output
topologies, depending if they are single phase (there will be
one figure only in the LCD panel) or three phase (there will be
three figures that correspond to the three phases).
NOT AVAILABLE measurement screens for each setting are
stated in table 6.
NOT AVAILABLE measurement screens according to UPS setting.
(III / III)
-N- (III / I)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.21
-
2.22
-
2.23
-
2.24
-
2.25
-
2.26
-
2.29
In case of being a frequency converter, a part from the NOT
AVAILABLE screens according to the setting, the following
ones will not be available too:
Converter with batteries: 2.7 and 2.8.
Converter with no batteries: 2.7, 2.8, 2.10, 2.11, 2.12
and 2.33.
Tab. 6. NOT AVAILABLE measurement screens according to the
UPS setting.
Screen 2.1: input voltages phase to phase (units 0.1 V).
Screen 2.2: three phase input voltages phases to neutral or
for single phase input phase to neutral (units 0.1 V).
Screen 2.3: input current per each phase for three phase
equipments or for the phase for single phase equipment (units
0.1 A).
Screen 2.4: three phase output voltages phases to neutral, or
for single phase output phase to neutral (units 0.1 V).
Screen 2.5: output current per each phase for three phase
equipments or for the phase for single phase equipment (units
0.1 A).
Screen 2.6: three phase inverter output voltages phases to
neutral, or for single phase inverter output phase to neutral
(units 0.1 V).
Screen 2.7: three phase bypass voltages phase to neutral or
for single phase bypass phase to neutral (units 0.1 V).
Screen 2.8: bypass current per each phase for three phase equip-
ments or for the phase for single phase equipment (units 0.1 A).
Screen 2.9: positive and negative DC bus voltages (units 0.1 V).
Screen 2.10: positive and negative battery voltages (units 0.1 V).
Screen 2.11: positive and negative battery charging currents
(units 0.1 A).
USER'S MANUAL
-L- (I / I)
-M- (I / III)
2.1
2.1
2.13
2.13
2.14
2.14
2.15
2.15
2.16
2.16
2.17
2.17
2.18
2.18
2.21
-
2.22
-
2.23
-
2.24
-
2.25
-
2.26
-
2.29
-
Screen 2.12: positive and negative battery discharging cur-
rents (units 0.1 A).
Screen 2.13: input apparent power of L1 (units 0.1 kVA).
Screen 2.14: input apparent power of L2 (units 0.1 kVA).
Screen 2.15: input apparent power of L3 (units 0.1 kVA).
Screen 2.16: input active power of L1 (units 0.1 kW).
Screen 2.17: input active power of L2 (units 0.1 kW).
Screen 2.18: input active power of L3 (units 0.1 kW).
Screen 2.19: total input apparent power and active power
(units 0.1 kVA and 0.1 kW).
Screen 2.20: input power factor of each phase in three phase
equipments or input power factor for single phase equipments
(units 0.01).
Screen 2.21: apparent output power of L1 (units 0.1 kVA).
Screen 2.22: apparent output power of L2 (units 0.1 kVA).
Screen 2.23: apparent output power of L3 (units 0.1 kVA).
Screen 2.24: active output power of L1 (units 0.1 kW).
Screen 2.25: active output power of L2 (units 0.1 kW).
Screen 2.26: active output power of L3 (units 0.1 kW).
Screen 2.27: total apparent and active powers (units 0.1 kVA
and 0.1 kW).
Screen 2.28: output power factor of each phase for three
phase equipments or output power factor for single phase
equipments (units 0.01).
Screen 2.29: total load of three phases (units 0.1%).
Screen 2.30: total input and output load (units 0.1%).
Screen 2.31: input, bypass and output frequencies (units
0.1 Hz).
Screen 2.32: rectifier, inverter and battery temperatures (units
1 ºC).
Screen 2.33: estimated backup time (units 1 minute).
Displayed measurements in screens 2.1 to 2.8, 2.20, 2.28
and 2.29 will be according to the input and output to-
pologies, depending if they are single phase (there will be one
figure only in the LCD panel) or three phase (there will be three
figures that correspond to the three phases).
7.3.4. ''PARAMETERS'' level (screen menu 3.0).
See fig 47.
Screen 3.1: In the first row, the time "hh:mm:ss" (hours/min-
utes/seconds) can be set and in the second row the date "dd/
mm/yy" (day/month/year) can be set.
Screen 3.2: In the first row, the display language can be
selected. Options:
"English"
ˆ
"Spanish"
ˆ
"French"
ˆ
"German"
ˆ
"Turkish"
ˆ
"Russian"
ˆ
In the second row, the Modbus Address can be set. The range
of addresses goes from 1 to 247.
SLC CUBE3+ PS UNINTERRUMPTIBLE POWER SOURCE
141

Publicité

loading