Télécharger Imprimer la page

Burkert 8026 Démarrage Rapide page 36

Masquer les pouces Voir aussi pour 8026:

Publicité

Les langues disponibles

Les langues disponibles

Red
Current
Transistor
LED
output
output
OFF
4-20 mA Switched
2)
OFF
4-20 mA Switched
2)
OFF
4-20 mA Switched
2)
1)
if the DIAG MODE function in the "Output.AC1" or "Output.AC2" menu is set to "22 mA"; otherwise, the current output delivers a standard current between
4 and 20 mA
2)
If the "PVAR" function in the "Output.TR1" and/or "Output.TR2" menu is set to "warning"; otherwise, the transistor outputs are operating according to the
programmed thresholds
30
All manuals and user guides at all-guides.com
Icon
Message displayed
in the Info menu
+ "W:Frequency"
"W:TRnPu too big"
"W:TRnPu 1:1 set"
english
Meaning
What to do
The input frequency is out
of range.
This message is displayed
if monitoring of the input
frequency is activated,
depending on the pro-
grammed thresholds
WARN LO and WARN HI
In "Pulse" mode, the vol-
ume input for a pulse is
incorrect.
In "Pulse" mode, the vol-
ume input for a pulse is
incorrect.
Type 8026 - 8036 - 8076
Maintenance and troubleshooting
Go into the "Sensor" function in the Diag-
nostic menu to read the value of the input
frequency.
check that the paddle is clean and that it ro-
tates freely on its axis or
check that the oval gears rotate freely.
check the installation.
Input an appropriate volume
check the K factor.
Input an appropriate volume
check the K factor.