11. Requirements for starting
11.1 Fundamental requirements
electrical voltage [230 V / 50 Hz ( 110 V / 50 / 60 Hz )].
sufficient quantity of water ( > 6 ltr. / min).
sufficient water pressure ( high pressure range > 20 bar )
( low pressure range > 4 bar flow pressure )
unlocked temperature limiting safety device.
(digital)thermostat, adjusted to the desired water temperature.
If these prerequisites are accomplished, the green control light at the front of the switch box should be "on".
If not, each item has to be checked.
11.2 Fundamental requirements for starting concerning the gas
At the entrance of the valve a gas pressure of at least 20 mbar must exist. (ball valve open and pressure measuring
at point 1 see picture 3 on page 11)
After the starting of the ventilator the air pressure must be > 2 mbar.
If not, check the ventilator motor, the ventilator entrance and the measuring hose.
11.3 Requirements for a stable flame.
Sufficient ionization current > 3 μ A.
For the measurement the plug of the ionization electrode has to be pulled off, and a micro ammeter has to be looped in.
The measuring has to be done during the starting period and during the operation of the burner.
If the ionization current is too low or not existing at all, verify the plug, the cable and the ionization electrode.
If necessary, readjust the electrode. In difficult situation you could retrofit a UV-cell.

12. Putting into operation

12.1 Guarantee the water supply
Open the water tap, start the pump,
Attention – to avoid the formation of steam bubbles at full loading of the burner, the water quantity may not fall below
6 Litres/min.!
12.2 Electrical connection
Verify, whether the correct tension exists at the machine.
Operating voltage: 230V / 50 Hz (110V / 50 / 60 Hz)
12.3 Gas connection
Verify, whether the ball valve is open and gas is there.
The gas pressure must be between 20 and 100 mbar.
12.4 Cold water operation
In case of cold water operation the main switch is "ON" and the thermostat is "0".
Or boiler off switch if a digital thermostat is installed.
12.5 Hot water operation
In case of hot water operation the main switch is "ON" and the thermostat regulated according to the required temperature.
12.6 Use of chemical substances
Cleaning processes by using chemical substances require the according special devices.
If these exist, the chemical tank must be filled and the chemical's metering valve must be opened.
Attention – if the chemical tank is empty and the metering valve is open, pressure will not build up.
If the pump runs for a longer period of time in this condition, this might lead to damages to the pump by cavitations!
12.7 Verification before each starting
Before putting into operation the machine the temperature limiting safety device, spraying device, pumps and hose
conduits should be checked as to their proper condition.
C O M B U S T I O N C H A M B E R G A S H E AT E D I N S T R U C T I O N S - R E G U L AT I O N S    
9