Amount of grease: refer to the plate on the motor. For the standard versions you can refer to the following table:
Type of bearing
Motor frame size
Quantity of grease
-
Lubrication interval: see TAB.III
û
û
ATTENTION!
Procedure for greasing
It is recommended to carry out lubrication with the group running following the procedure below:
-
Open the caps/valves for loading and unloading the grease;
-
Clean the grease insertion holes;
-
Check that the lubrication channel is clean;
-
Insert the necessary quantity of grease using the proper grease nipple;
-
Run the group for about 30 minutes to let the excess grease to come out;
-
Close the caps/valves.
If the operation is to be carried out with the motor stopped:
-
introduce less grease than necessary;
-
run the motor for a few minutes at rated speed;
-
stop the motor and top up with the necessary grease;
-
Run the group for about 30 minutes to let the excess grease to come out;
Characteristics of the greases to be used for normal operating conditions (Tamb = -10°C + 40°C, Tmax bearings = 110°C):
-
Base grease: mineral or PAO
-
Thickener: lithium soap
-
Temperature range: -30°C/+120°C
-
NLGI class: 2 or 3
-
Base oil viscosity at 40°C: 110 mm
Some types of grease that can be used:
EXXON MOBIL - UNIREX N2 – N3
EXXON MOBIL - MOBILITH SHC100
SHELL - GADUS S5 V100 2
SHELL - GADUS S2 V100 2
TOTAL - MULTIS COMPLEX S2A
KLUBER - KLUBERPLEX BEM 41-132
FAG - MOBILITH SHC 100
For different conditions of use, contact Sulzer technical assistance or refer to the specific documentation of the bearing
s. Dispose of residual and used grease in compliance with local regulations.
û
·
7.2.3 CHECK OF THE INSULATION RESISTANCE
Measure the insulation resistance with a megohmmeter at 500 Vdc.
Measure between cables and ground. It is recommended to isolate and test the individual phases separately.
During the test on one of the phases the others must be grounded.
225...
DE
30g
Do not mix different types of grease.
Do not introduce contaminants into the bearing, the housing or the grease.
/s
2
Do not make changes to the product without prior authorization.
Before carrying out any operation, disconnect the power supply and make sure that it cannot be restored:
comply with the requirements of EN 50110-1 "Working in the absence of voltage" during any type of
intervention.
Keep the manual for future reference - For more informations visit www.sulzer.com
6314-Z
250...
NDE
DE
27g
30g
- Translation of the original instructions
6316
280...
NDE
DE
27g
100g
NDE
100g

Publicité

Table des Matières
loading

Produits Connexes pour Sulzer MT

Ce manuel est également adapté pour:

Mm

Table des Matières