Contrôles
3-phase
power
input
Regen
terminals
+10 V DC
0 V DC - 10 V DC
0/4-20 mA
0 V DC - 10 V DC
0/4-20 mA
14
14
Illustration 14.1 Schéma de câblage
130
®
VLT
Parallel Drive Modules
L
230 V/24 V Power supply
N
230 V A C
50/60 Hz
91 (L1)
92 (L2)
93 (L3)
95
PE
88 (-)
89 (+)
50 (+10 V OUT)
A53 U-I (S201)
53 (A IN)
ON=0–20 mA
A54 U-I (S202)
OFF=0–10 V
54 (A IN)
55 (COM A IN)
12 (+24 V OUT)
13 (+24 V OUT)
18 (D IN)
19 (D IN)
20 (COM D IN)
27
(D IN/OUT)
24 V
0 V
29
(D IN/OUT)
24 V
0 V
32 (D IN)
33 (D IN)
37 (D IN) - option
Danfoss A/S © 11/2016 Tous droits réservés.
Switch mode
Power supply
10 V DC
24 V DC
15 mA
200 mA
+
-
+
-
P 5-00
24 V (NPN)
0 V (PNP)
24 V (NPN)
0 V (PNP)
S801/Bus Term.
24 V (NPN)
OFF-ON
0 V (PNP)
ON=Terminated
OFF=Open
5 V
24 V (NPN)
0 V (PNP)
S801
RS485
Interface
24 V (NPN)
0 V (PNP)
24 V (NPN)
0 V (PNP)
(U) 96
(V) 97
(W) 98
(PE) 99
(R+) 82
Brake
resistor
(R-) 81
Relay1
03
240 V AC, 2A
02
400 V AC, 2A
01
Relay2
06
240 V AC, 2A
05
400 V AC, 2A
04
(COM A OUT) 39
Analog output
0/4–20 mA
(A OUT) 42
1
Brake Temp
(NC)
2
0 V
RS485
(P RS485) 68
(N RS485) 69
(COM RS485) 61
(PNP) = Source
(NPN) = Sink
Motor