Maintenance
6.2

Breaking In New Machines

Run the generator at least 60–100% of continuous load for the first 100 hours.
Change engine oil and replace oil filter after the first 100 hours.
6.3

Resetting the Periodic Maintenance Timer

After maintenance has been performed on the generator, it is necessary to reset
the periodic maintenance timer.
Resetting
The periodic maintenance timer can be reset while viewing the maintenance timer
from
pre-alarm or hours remaining. To reset the periodic maintenance timer while
Maintenance
viewing these menus, press and hold the reset button (6) for 10 seconds.
Timer Menus
If pre-alarm is active:
Main screen
METERING > ALARM STATUS > PRE-ALARMS
If pre-alarm is not active:
METERING > ENGINE
METERING > RUN STATISTICS > CUMULATIVE > CUMULATIVE
Resetting
The periodic maintenance timer can also be reset from the main menu.
from Main
1. To access the main menu, press the right arrow button (1) on the keypad (g).
Menu
Note: If there are active alarms or pre-alarms, press the left arrow button (4) three
times to access the main menu.
2. Using the up/down arrow buttons (2,3), select SETTINGS and press the right
arrow button.
3. Select SYSTEM PARAMETERS. Press the right arrow button (1).
4. Select SYSTEM SETTINGS. Press the right arrow button (1).
5. Select MAINT RESET. Press the check mark button (5).
68