Using the LCD Panel and Keypad
5.6

Changing / Disabling Low Fuel Fault

See graphic: wc_gr005938
5.6.1
5.6.2
5.6.3
5.6.4
5.6.5
5.6.6
5.6.7
5.6.8
5.6.9
The low fuel fault value can be changed or disabled through the
diagnostics menu. (For example, you may wish to reduce the value so
that the machine operates for a longer period before running out of
fuel.)
Note: The engine will shut down if the machine runs out of fuel.
Follow the steps below to change or disable the low fuel fault.
To access the main menu, press the right arrow button (1) on the
keypad (g).
Note: If there are active alarms or pre-alarms, press the left arrow button (4)
three times to access the main menu.
Using the up/down arrow buttons (2,3), select SETTINGS and press
the right arrow button.
Select ALARM CONFIGURATION. Press the right arrow button.
Select ALARMS. Press the right arrow button.
Select LOW FUEL LEVEL. Press the right arrow button.
Select THRESHOLD. Press the check mark (5).
Enter your password. (See Entering Passwords for more information.)
Change the default Low Fuel Level value to zero (0) or the desired
figure. Press the check mark button to accept the change, or the reset
button (6) to cancel. Anything less than 5 will disable the automatic
shutdown feature.
Exit by repeatedly pressing the left arrow button until the LCD panel
display returns to monitoring status.
Note: The fuel level reading on the display will not drop below 5%.
Mobile Generator
64
wc_tx001182gb.fm