Ingersoll Rand X8I Mode D'emploi page 37

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 221
S02 – AI Auxiliary Digital Input
1
1
1 1
The function of the Auxiliary input.
01:DI
Digital Input
No defined function but status (0=normal,
1=activated)
02:T1
Override > Table 1
03:T2
Override > Table 2
04:T3
Override > Table 3
05:T3
Override > Table 4
06:TS
Override > Standby
07:AA Remote Alarm (always active)
08:AR
Remote Alarm (active when unit running,
inhibited when unit stopped or in Standby)
09:TA
Remote Trip (always active)
10:TR
Remote Trip (active when unit running, inhibited
when unit stopped or in Standby)
11:SS
Remote Start/Stop
NO (Normally Open)
The selected function is activated when the input is
closed circuit (input terminals are connected together by
remote volt-free contacts)
NC (Normally Closed)
The selected function is activated when the input is open
circuit (input terminals are open circuit)
S02 – AO Auxiliary Output Function
A
O
The function of the Auxiliary output 'volt-free' relay
contacts.
01:AF
Any Alarm (Warning), Shutdown (Trip) or Compressor Not
Available.
02:AT
Any Shutdown (Trip) or Compressor Not Available.
03:CF
Any compressor Alarm (Warning), Shutdown (Trip) or Not
Available
04:CA
Any compressor Alarm (Warning)
05:CT
Any compressor Shutdown (Trip) or Not Available
06:SF
Any unit Alarm (Warning) or Shutdown (Trip)
07:ON System On
Unit Started and Active, including Pre-Fill period and
Standby mode (not active when unit stopped)
08:SA
Unit Active, including Pre-Fill period (not active when unit
stopped or in standby mode)
09:LP
10:HP
11:PO Pressure Control Override
Normal, or Pressure Schedule' operation is being manually
overriddenThe function of the Auxiliary output 'volt-free'
relay contacts.
S02 - ER Error Log Reset
This parameter clears and resets the 'Error Log' . The
default setting for this parameter is
Error Log Reset is disabled)
The values for this parameter are:
" " Error log reset is disabled
"
" Error log reset enabled. Adjust the item setting to
' ' and press ENTER. The display will return to the main
menu and all existing entries in the error log will be
permanently deleted.
37
11 1
1
Any Fault
Any Trip
Compressor Fault
Compressor Alarm
Compressor Trip
System Fault
System Active
Low Pressure Alarm
High Pressure Alarm
. (Represents the

Publicité

Table des Matières
loading

Table des Matières