Paragraaf 5  InstallatieOverzicht - Ingersoll Rand X8I Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 221
PARAGRAAF 5  INSTALLATIEOVERZICHT
SPECIFICATIONS
Dimensions 13.4" x 9.45" x 6.0"
340mm x 241mm x 152mm
Weight
16.5lb (7.5kg)
Mounting
Wall, 4 x screw fixings
Enclosure
IP65, NEMA 4
Supply
230Vac +/- 10%, 50 Hz
115Vac +/- 10%, 60 Hz
Power
100VA
Temperature 32°F to 115°F
(0°C to 46°C)
Humidity
0% to 95% RH
(non-condensing)
Local Disconnect (Breaker) Box
Fused for 100VA
Power Cable
3 conductor (N, L, E)
(Sized in accordance with local
electrical and safety regulations).
PRESSURE TRANSDUCER CABLE
2 Conductor Cable, 18 Gauge Stranded
Earth Shielded
No Greater Than 330FT (100M)
24VDC Control Voltage
X8I X05 CONNECTOR
PT CONNECTOR
25
+VDC Pin #3
26
Signal Pin #1
Reference X8I Operations Manual for Pressure
Sensor Connection Details
PRESSURE TRANSDUCER
To Plant Air
System
RECEIVER
Ingersoll
Ingersoll
Rand
Rand
102 psi
102 psi
I/O
ir-485
Direct To
S3
Ingersoll Rand Automation
Model X8I
Ingersoll Rand
psi
102
1
18:35 #2
Supply Voltage Cable
On/Off
Switch
Pressure Transducer Cable
ir-PCB
DRIP LEG
Reference X8I Application and Interconnect Guide For
Wiring Connections Between The X8I, The ir-PCB,
and The Compressor
From Air
Reference X8I Application and Interconnect Guide For
Compressors
Wiring Connections Between The X8I, The ir-485 or irV-
485 Gateway and The Compressor, S3 Direct Connects, and
Optional Special Application Interface Boxes
ir-PCB
1
3
2
4
CAP
5
7
6
8
EXP RS485 Network Cable
EXP RS485 NETWORK CABLE
Belden 9841 or Equivalent
In Grounded Conduit
No Greater Than 33FT (10)
RS485 Network Cable
RS485 NETWORK CABLE
Belden 9841 or Equivalent
In Grounded Conduit
No Greater Than 4000FT (1219M)
Ir-PCB Compressor #1
Ir-PCB Compressor #2
Control Cable
Control Cable
7 Conductor Cable, 18 Gauge, Stranded, Earth Shielded
Single Conductor Wire, 18 Gauge Stranded, Quantity (7)
In Grounded Conduit No Greater Than 330FT (100M)
Communication Network Refer to the X8I Application and
Interconnect Guide For Wiring Details and Connectivity.
Ingersoll
Rand
102 psi
ir-485
IR (Non- Nirvana) Compressors
IntelliSys "Red Eye", SG and SE
VSD
OR
From VSD Pressure
Transducer
To VSD Pressure
Transducer Input
irV-485
Nirvana Compressors
20HP (15KW) and Above
9
The Maximum Number of Compressors Controlled By
The X8I Is Eight (8).
The Maximum Number Of Direct ir-PCB Connections
To The X8I is Four (4) .
Any Combination Of Compressor Connection Methods
May Be Used As Long As the Maximum Number Of
Compressors (8) Is Not Exceeded.
The EXP Will Add Another (4)
Direct ir-PCB connections. This
Would Allow A Total Of (8)
Compressors To Be Connected
And Controlled Via The ir-PCB.
EXP
OPTIONAL
ir-PCB
ir-PCB COMPRESSOR CONTROL CABLE
OR
24VAC Control Voltage
The RS485 Network is a Serial, Point to Point
ir-485 Gateway
Ingersoll
Rand
For All
102 psi
irV-485 Gateway
For All
EX

Publicité

Table des Matières
loading

Table des Matières