Limit and Force Adjustment

To reduce the risk of SEVERE INJURY or DEATH:
Without a properly installed safety reversal system, persons
l
(particularly small children) could be SERIOUSLY INJURED or
KILLED by a moving gate or door.
Too much force on gate/door will interfere with proper operation of
l
safety reversal system.
NEVER increase force beyond minimum amount required to move
l
gate/door.
Introduction
Your operator is designed with electronic controls to make travel limit
and force adjustments easy. The adjustments allow you to program
where the gate/door will stop in the open and close position. The
electronic controls sense the amount of force required to open and close
the gate/door. The force is adjusted automatically when you program the
limits but should be fine tuned using the REVERSAL FORCE dial on the
control board (refer to Fine Tune the Force section) to compensate for
environmental changes. The limit setup LEDs (located next to the SET
OPEN and SET CLOSE buttons) indicate the status of the limits, refer to
the table to the right.
The limits can be set using the control board (below) or a remote control
(refer to Limit Setup with a Remote Control in the Appendix). Setting the
limits with a remote control requires a 3-button remote control
programmed to OPEN, CLOSE, and STOP.
NOTE: The TEST buttons on the control board will not work until the
limits have been set and the required entrapment protection devices are
installed.
Initial Limits and Force Adjustment
The gate/door MUST be attached to the operator before setting the
limits and force.
1. Press and release the SET OPEN and SET CLOSE buttons
simultaneously to enter limit setting mode.
2. Press and hold one of the MOVE GATE buttons to move the
gate/door to the open or close limit.
3. Press and release the SET CLOSE or SET OPEN button depending
on which limit is being set.
4. Press and hold one of the MOVE GATE button to move the gate/door
to the other limit.
5. Press and release the SET CLOSE or SET OPEN button depending
on which limit is being set.
6. Cycle the gate/door open and close. This automatically sets the force.
When limits are set properly the operator will automatically exit limit
setting mode.

ADJUSTMENT

NEVER use force adjustments to compensate for a binding or sticking
l
gate/door.
If one control (force or travel limits) is adjusted, the other control
l
may also need adjustment.
After ANY adjustments are made, the safety reversal system MUST be
l
tested. Gate/door MUST reverse on contact with an object.
SET
OPEN
LED
OFF
BLINKING
BLINKING
ON
ON
1
17
LIMIT SETUP LEDS
SET
OPERATOR
CLOSE
MODE
LED
OFF
NORMAL MODE
BLINKING
LIMIT SETTING
MODE
ON
LIMIT SETTING
MODE
BLINKING
LIMIT SETTING
MODE
ON
LIMIT SETTING
MODE
2
6
EXPLANATION
Limits are set
Limits are not set
Open limit is not set
Close limit is not set
Limits are set
3
4
5