positioned the gate in intermediate position, check the correct ignition of LEDS DL2, DL3,
DL4, DL5, DL8.
In case of no ignition of the LEDS, always with gate in intermediate position, check the
following and replace any faulty components.
DL2
switched off
Faulty Stop button
DL3
switched off
Faulty opening limit switch
DL4
switched off
Faulty closing limit switch
DL5
switched off
Faulty photocells
DL8
switched off
Faulty safety edge (In case the edge is not connected, carry out
jumper between COM and EDGE)
During functioning with personnel present, with DIP 1 at ON, check that during opening the
green DL6 LED switches on and that during closing the red DL7 LED switches on. If not, invert
clamps V and W on the motor terminal board.
After having carried out the various connections and having supplied voltage, all the LEDS
are switched off.
The motor opens and closes, but it has no strength and moves slowly.
The gate opens but does not close after the time set.
The gate does not open or close by activating the various OPEN, CLOSE, K and RADIO buttons. Faulty safety edge contact.
Motor with encoder (DIP n° 7 at ON) enabled.
The gate opens and closes only for brief intervals.
By activating the K or CLOSE button the gate does not move.
The slowing phase is not performed.
FINAL OPERATION -
Fit the gasket
FAULT
The gasket shall be fitted only at the end of the installation, before you mount the case.
The gasket is fitted
Check the integrity of fuses F1 and F2.
In case of interrupted fuse use only of adequate value
Check trimmers TORQUE and LOW-SPEED adjustment.
Ensure to have set DIP 3 at ON.
Button K BUTTON always inserted in automatic functioning mode (DIP 5 OFF).
Replace button or switch of the selector switch.
Failed edge self-test => check the connections between electronic board and edge feeder.
Attention: if not using a feeder for edges, DIP 12 must be at OFF position.
Faulty photocells contact with DIP 6 OFF.
Fix or replace the relative contact.
Check encoder connection and eventually replace.
Impulse K or CLOSE always inserted.
Check and replace any buttons or micro-switches of the selector switch.
Ensure that DIP 9 is at position OFF (slowing enabled).
Learn the times through procedure from DIP 2.
Check trimmer LOW-SPEED adjustment.
Close the case
35
SOLUTION
F2 = 5A
F1 = 100mA.
Motor ready