7MF4010
Protection antidéflagrante selon FM
Marquage
Température ambiante admissible T
Entity parameters
Protection antidéflagrante selon CSA
Marquage
Température ambiante admissible T
Entity parameters
14
Instructions de service
Certificate of Compliance 300849
(XP/DIP) ou (IS)
CL I, DIV 1, GP ABCD T4
CL II, DIV 1, GP EFG; CL III
CL I, ZN 0/1 AEx ia IIC T4
(NI)
CL I, DIV 2, GP ABCD T4
CL II, DIV 2, GP FG; CL III
= T4: --30 à +80 _C
a
Selon "Control Drawing" A5E00072865A
U
= 30 V,
i
l
= 100 mA,
i
P
= 750 mW,
i
L
= 0,75 mH,
i
C
= 21 nF
i
Certificate of Compliance 2001.1153651
(XP/DIP) ou (IS)
CL I, DIV 1, GP ABCD T4
CL II, DIV 1, GP EFG; CL III
Ex ia IIC T4
CL I, DIV 2, GP ABCD T4
CL II, DIV 2, GP FG; CL III
= T4: --30 à +80 _C
a
Selon "Control Drawing" A5E00072865A
U
= 30 V,
i
l
= 100 mA,
i
P
= 750 mW,
i
L
= 0,75 mH,
i
C
= 21 nF
i