Wilo CRONOLINE-IL-E Série Notice De Montage Et De Mise En Service page 124

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English
Classification No.
E051
E052
Electronics
E070
errors
E071
E072
E073
E075
E076
E077
E078
E096
E097
E098
E121
E122
E124
Impermissi-
E099
ble combina-
torics
Table 11: Error table
Additional explanations of error
codes
116
Fault
Cause
Impermissible DP/MP
Different pumps
combination
DP/MP communica-
Cable MP communication
tions time-out
defective
Internal communica-
Internal electronics error
tion error (SPI)
EEPROM error
Internal electronics error
Power section/fre-
Internal electronics error
quency converter
Impermissible elec-
Internal electronics error
tronic module number
Charging relay
Internal electronics error
defective
Internal transformer
Internal electronics error
defective
24 V operating voltage
Differential pressure sen-
for differential pres-
sor defective or connected
sure sensor defective
incorrectly
Impermissible motor
Internal electronics error
number
Infobyte not set
Internal electronics error
FlexPump data record
Internal electronics error
missing
FlexPump data record
Internal electronics error
invalid
Motor PTC short-cir-
Internal electronics error
cuit
Interruption to NTC
Internal electronics error
power element
Interruption to NTC
Internal electronics error
electronic module
Pump type
Different pump types have
been interconnected
Error E021:
Error 'E021' indicates that the pump requires more power than is per-
mitted. To ensure that the motor and electronic module do not suffer
irreparable damage, the drive protects itself by switching the pump
off if an overload lasts more than 1 minute.
The most common causes of this error are a pump that is configured
too small, especially when pumping viscous fluids, or an excessive
volume flow in the system.
When this error code is displayed, there is not an error in the electronic
module.
Error E070; possibly combined with error E073:
If additional signal lines or control cables are connected to the elec-
tronic module, the effects of EMC (immission/interference resistance)
may interrupt communication. This results in error code E070 being
displayed.
Remedy
Request customer service
Check cable and cable
connections
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Check differential pressure
sensor connection
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Error type
HV
AC
F
F
E
E
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
WILO SE 12/2017

Publicité

Table des Matières
loading

Table des Matières