Wilo CRONOLINE-IL-E Série Notice De Montage Et De Mise En Service page 112

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English
No.
Designation
5.7.5.0
Switching fre-
quency
5.7.6.0
SBM function
5.7.7.0
Factory setting
5.8.0.0
Other settings 2
5.8.1.0
Pump kick
5.8.1.1 Pump kick
active / inactive
5.8.1.2 Pump kick
Time interval
5.8.1.3 Pump kick
Speed
6.0.0.0
Fault acknowl-
edgement
7.0.0.0
Access disable
104
Type
Symbol Values/explanations
HIGH
High switching frequency
(factory setting)
MID
Medium switch frequency
LOW
Low switching frequency
±
Setting for behaviour of signals
SBM run signal
SBM readiness signal
SBM mains on signal
±
OFF (default setting)
Settings are not changed by
confirming.
ON
Confirming will reset the set-
tings to factory settings.
Caution!
All manual settings will be lost.
ON (factory setting)
Pump kick is activated.
OFF
Pump kick is deactivated.
±
Can be set between 2 h and 72 h
in 1 h steps
±
Can be set between the pump's
minimum and maximum speeds
±
For additional information, see
chapter 11.3 "Acknowledge
fault" on page 117.
±
"Access disable" inactive
(changes possible)
(for further information, see chap-
ter 8.6.7 "Activating/deactivating
access disable" on page 97).
Display conditions
Carry out the switch over/
change only when the pump
is at a standstill (not when
the motor is running)
Is not displayed when access
disable active. Is not dis-
played when building man-
agement system active
Is not displayed when access
disable active. Is not dis-
played when building man-
agement system active
For parameters that are
changed by a factory setting,
see chapter 13 "Factory set-
tings" on page 123.
Not displayed for all pump
types.
Is not displayed if pump kick
is deactivated
Is not displayed if pump kick
is deactivated
Only displayed if an error is
present
WILO SE 12/2017