Starting The Ups On Battery - Eaton Powerware Série Guide D'installation

Masquer les pouces Voir aussi pour Powerware Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

5.
Select MENU from the system status screen, then select
CONTROL, OUTPUT CONTROL, UPS TO ONLINE, and OK to
confirm.
The LCD displays a confirmation message and the
illuminates solid. The UPS is now in Normal mode and supplying
power to your equipment.
If the
indicator is flashing, check the UPS status from the front
panel to view the active alarms. Correct the alarms and restart if
necessary.
6.
Turn on the protected equipment.

Starting the UPS on Battery

NOTE Before using this feature, the UPS must have been powered by utility power at least
once.
To start the UPS on battery without utility power connected:
1.
Turn off all protected equipment before starting up the UPS.
2.
Switch all output circuit breakers to the ON (
3.
Press any button on the front panel display to activate the screen.
4.
Wait for the front panel LCD to illuminate.
The LCD displays the startup screen for five seconds, then displays
the system status screen. The fans run. The
quickly then slowly, indicating that the UPS has entered Standby
mode.
5.
Select MENU from the system status screen, then select
CONTROL, OUTPUT CONTROL, UPS TO BATTERY, and OK to
confirm.
The LCD displays a confirmation message and the
illuminates solid. The UPS is now in Battery mode and supplying
battery power to your equipment.
6.
Turn on the protected equipment.
®
Eaton
9140 (9910-E82/E83) UPS Installation Guide for IBM
| ) position.
indicator flashes
S
®
Applications
164201715 Rev 2
www.eaton.com/ibm
OPERATION
indicator
indicator
49

Publicité

Table des Matières
loading

Table des Matières