OPERATION
Table 10. User Settings
Description
O/P (Output) Frequency*
O/P (Output) Voltage
Buzzer Alarm
Battery Pack
Battery Test
DC Start
Auto Restart
UPS ID
* Changes to these options should be made before turning on the UPS (while the UPS is in Standby mode); otherwise,
the changes do not take effect.
44
®
Eaton
9140 (9910-E82/E83) UPS Installation Guide for IBM
www.eaton.com/ibm

User Settings

The following table displays the options that can be changed by the
user.
Available Settings
[50 Hz][60 Hz][Auto]
NOTE If Auto is selected, input frequencies
<55 Hz are set to 50 Hz, and input frequencies
>55 Hz are set to 60 Hz. O/P Frequency
changes from Auto to the sensed frequency
setting.
[200V][208V][220V][230V][240V][Auto]
NOTE If Auto is selected, input voltages
<220V are set to 208V, and input voltages
>220V are set to 230V. O/P Voltage changes
from Auto to the sensed voltage setting.
[Enabled][Disabled]
1 through 5
NOTE A value of 1 indicates the UPS internal
batteries only. See "Configuring the UPS for
EBMs" on page 52.
[Enabled][Disabled]
NOTE When Enabled, the battery test runs
automatically approximately every three
months.
[Enabled][Disabled]
[Enabled][Disabled]
0 through 3
NOTE This option is not used.
Default Setting
Auto
Auto
Enabled
1
Enabled
Shipped: Disabled
After one startup and
shutdown sequence: Enabled
Enabled
0
S
®
Applications
164201715 Rev 2