Storing/ Fault/ Störung
Dérangement/ Guasti/ Błędy w pracy urządzenia
Fault
Cause
code
E103
Bypass fault.
E104
Extract fan defective.
E105
Supply fan defective.
The temperature sensor that
E106
measures the outdoor tempera-
ture is defective.
The temperature sensor that
E107
measures the temperature of the
extract air is defective.
If present: The temperature sen-
E108
sor that measures the external
temperature is defective.
If present: The RH-sensor that
E111
measures the huminity is defec-
tive.
Dip switches on control board
not set correctly.
Note!
If mode 2 of a multiple switch does not work, the modular connector of the multiple switch has been connected the wrong way round.
Cut off one of the RJ connectors to the multiple switch and mount a new connector the other way round.
57
Action appliance
- None.
(Current too low ĺ stepper motor not
correctly connected or effective;
current too high ĺ short-circuit in wiring
or stepper motor)
- Both fans are switched off.
- Preheater is switched off.
- Postheater is switched off.
- Restart every 5 minutes.
- Both fans are switched off.
- Preheater is switched off.
- Postheater is switched off.
- Restart every 5 minutes.
- Both fans are switched off.
- Preheater is switched off.
- Bypass closes and is blocked.
- Bypass closes and is blocked.
- If applicable: Postheater is switched off.
- If applicable: Geo heat exchanger is swit-
ched off.
- Appliance continues to operate
- Appliance does nothing; red fault LED on
multiple switch is not activated either.
EVOTHERM 150F
Action installer
đ „—ke the volt—ge from the —ppli—n™eċ
đ ghe™k ™onne™tion stepper motorĎ re-
place wiring or stepper motor
đ „—ke the volt—ge from the —ppli—n™eċ
đ ‚epl—™e extr—™t f—nċ
đ fut volt—ge ˜—™k on —ppli—n™eĎ p—ult
will automatically be reset.
đ ghe™k ™—˜lingċ
đ „—ke the volt—ge from the —ppli—n™eċ
đ ‚epl—™e
đ €ut volt—ge ˜—™k on —ppli—n™eĎ p—ult
will automatically be reset.
đ ghe™k ™—˜lingċ
đ „—ke the volt—ge from the —ppli—n™eċ
đ ‚epl—™e temper—ture sensor
đ €ut volt—ge ˜—™k on —ppli—n™eĎ f—ult will
automatically be reset.
đ „—ke the volt—ge from the —ppli—n™eċ
đ ‚epl—™e indoor temper—ture
sensor
đ ‚epl—™e extern—l temper—ture
sensor
đ „—ke the volt—ge from the —ppli—n™eċ
đ ‚epl—™e ‚rġsensorċ
đ €ut dip swit™hes in™orre™t positionċ
(see § 9).
7
GB