15.2.3.2 Cable entries and external sockets
There are cable glands and plug sockets in the bottom of
the SmartPSUk2. The socket for the remote PSk2 connection
is pre-wired and pre-assembled in the SmartPSUk2 hous-
ing. Cables of accessories which are fed through the cable
glands have to be fixed tightly in the glands for strain re-
lief and sealing.
The left two cable glands are designed to take the DC out
cables. The connection socket for the SmartPSUk2 to PSk2 is
located on the bottom.
The centre two cable glands are designed for the DC input
from the PV array.
The right large cable gland is designed for 3 phase AC input
from the grid or a generator.
Figure 60: Bottom view of SmartPSUk2
SmartSolution

15.2.3.3 Wiring

Power in- and output
(DC) Solar input voltage (open circuit) must not exceed:
U
= 850 V DC
max
(Even in cloudy weather, the open circuit voltage will be
near maximum.)
(AC) Generator or grid input voltage must not exceed:
U
= 380/400/415V AC (3-phase) at 50-60 Hz
nom
The following cable sizes are minimum recommendations
depending on the size of PSk2 system being used.
PSk2
DC
system
output
cable
PSk2-7
2.5 mm²
PSk2-9
2.5 mm²
PSk2-15
4 mm²
PSk2-21
6 mm²
PSk2-25
10 mm²
PSk2-40
16 mm²
The values in the table are for ambient temperatures of up
to 35 °C. If you expect higher temperatures, use next larg-
er cable size.
Ensure all terminals are tightened, a torque of 4-5 Nm is
recommended.
All screw terminals should be tightened when any system
maintained is carried out as they can become loose as the
copper cables relax, expand and contract.
Do not use cable ferrules with the screw connections.
85
AC
AC
input
input
cable
cur-
rent
2.5 mm²
15 A
2.5 mm²
20 A
4 mm²
25 A
6 mm²
38 A
10 mm²
45 A
16 mm²
70 A