Maintenance And Repair; Maintenance Intervals; Maintenance Work; Repair Work - Wilo Control MS-L 2x4kW Notice De Montage Et De Mise En Service

Masquer les pouces Voir aussi pour Control MS-L 2x4kW:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 43
English
waste disposal authorities, or the supplier from
whom the product was purchased.

9. Maintenance and repair

POTENTIALLY fatal danger due to electrical
voltage!
There is a risk of fatal electric shocks oc-
curring when performing work on the open
switchgear. During all work, the switchgear
must be disconnected from the electricity
network and secured against reactivation
without permission. All electrical work must
be carried out by a qualified electrician.
After completing maintenance or repair work,
the switchgear must be connected according to
the "Installation" section and activated as under
"Commissioning".
Maintenance or repair work and/or con-
structional changes that are not listed in this
operating and maintenance manual may only be
carried out by the manufacturer or by author-
ised service centres.

9.1. Maintenance intervals

To ensure reliable operation, various maintenance
tasks must be carried out regularly.
NOTE
When used in sewage lifting units inside build-
ings or on land plots, the maintenance intervals
and work shown in DIN EN 12056‐4 must be
adhered to.
Before initial commissioning or after a longer
period of storage:
• Clean the switchgear
Yearly
• Visual inspection of individual components

9.2. Maintenance work

Prior to maintenance work, the switchgear must
be switched off as described under "Temporary
shutdown". Maintenance work may only be car-
ried out by qualified persons.
9.2.1. Clean the switchgear
Use a damp cotton cloth to clean the switchgear.
Do not use any aggressive or scouring cleaners
or fluids!
9.2.2. Visual inspection of individual components
Have the individual components checked for wear
by a qualified electrician or Wilo Customer Service
(e.g. melting of protective contacts, deformation
of plastic parts).
If severe wear is identified, have the affected
components replaced by a specialist electrician or
Wilo Customer Service.
40
MAINTENANCE AND REPAIR

9.3. Repair work

Prior to repair work, the switchgear must be
switched off as described under "Final shutdown"
and all power supply cables dismantled. Repair
work must be carried out by an authorised service
centre or Wilo Customer Service.

10. Troubleshooting and possible solutions

DANGER due to electrical voltage!
Improper procedures during electrical work
may result in fatal injuries caused by electrical
voltage! Such work may only be carried out by
a qualified electrician.
Potential faults are indicated visually and audibly.
According to the fault shown, the connected
pump or signal transmitter must be checked for
correct operation and replaced if necessary.
Only perform this work if suitably qualified
personnel are available. Electrical work must be
carried out by qualified electricians for instance.
We recommend always having this work carried
out by Wilo Customer Service.
Unsanctioned modifications to the switchgear are
made at the operator's own risk and release the
manufacturer from any warranty obligations.

10.1. Acknowledging faults

After a fault occurs, a visual and audible warning is
output.
By briefly pressing the Buzzer OFF/reset button,
the audible alarm is deactivated and collective fault
signal relay (SSM) acknowledged.
When held down for longer (min. 1 sec), the fault is
acknowledged and the control is reenabled.
A fault can only acknowledged once it has been
eliminated!

10.2. Fault signals

LED lights up yellow
Cause: The set service interval has expired
Solution: Perform maintenance on the unit and have
the counter reset by Wilo Customer Service
LED flashes yellow
Cause: The monitored operating parameters have
been exceeded
Solution: Check the settings on the unit and have
the counter reset by Wilo Customer Service
LED lights up red
Cause: permitted rated current has been exceeded,
excess current release has been initiated
Solution: Check pump and setting of DIP switch 1
LED flashes red
Cause: Rated current below 300 mA during opera-
tion or phase L2 missing
Solution: Check mains connection of switchgear
and pump connection
WILO SE 02-2018 V05 DIN A4