Design of the on-site circuit breaker
Danger
Fire hazard due to device overload.
Fire hazard due to device overload in case of wrong
design of the on-site circuit breaker.
The nominal current of the selected circuit breaker must
not exceed the specifications on the nameplate.
The EU versions of the devices (Xtra E, Xtra R, Trend E,
Premium E und Premium R) are supplied without integrated
circuit breakers. The circuit breakers must be scaled
according to the specifications on the name plate, the
required charging power, the supply line (line length, cable
cross-section) to the charging station and national
regulations.

5.4.3 Terminals

Fig. 14: Terminals for the supply line (example)
Connect the supply line:
1. Strip the supply cable over a length of 370 mm and
remove the core insulation over a length of 12 mm.
2.
Connect the cores
2
terminal block
according to the circuit diagram. The
1
protective earth conductor (PE) must be longer than all
other conductors!
3. Check that the individual cores are properly connected
and that the screws are tightened.
of the supply cable to the
16