SBM: A collective run signal (SBM) can be attached to the master
x
for a central control point. The contact may only be connected to
the master. The reading is valid for the entire unit. On the IR
monitor, this signal can be programmed as a single (EBM) or a
collective run message (SBM). For single run message, the con-
tact must be connected to each pump.
The EBM/SBM is active as long as the motor is operating. The
signal disappears when the motor has stopped.
ESM/EBM: If the SSM is programmed as ESM on the
CAUTION!
IR monitor, also the SBM will function as EBM
(always same functionality for fault signal and run
message).
Single pump operation:
1
2
Setting when first used /
Menu order during standard use
LC display
7.4.1 After powering up
When started up for the first time, the pump uses the factory set-
tings. For the individual setting and adjustment of the pump, the
operation menu (see section 7.4.2) and the service menu (see sec-
tion 7.4.3) are used.
Changing the settings for the differential pressu-
CAUTION!
re sensor may cause malfunctions!
The factory settings are configured for the WILO differential pres-
sure sensor provided.
Setting values: input IN1 = 0-10 V
pressure value correction = ON
If the Wilo differential pressure sensor is used, these settings must
remain unchanged!
Changes are only required when using other differential pressure
sensors.
After switching on the module, all symbols appear on the display for 2 s.
Next, the current status is shown.
Current (basic) setting (factory setting):
e.g. H 12,0 m
f Set delivery height H
| H max (factory setting dependent
on pump type)
f control sytem ∆p-c
on
f pump switched on
Changing the differential pressure setpoint:
Turn the tuning button. The new differential pressure setpo-
int blinks.
Press button to store the new setting.
Press button (> 2 sec).Menu
displayed.
ENGLISH
Setting
= 12,0 m at the same time
S
X
(the operation menu) is
3
35