3.4.1.1 change battery type
Configuration according to 12V,24V,36V,48V battery type*
Description of the
battery type
FACTORY SETTING (by default)
AGM** / GEL/ Sealed
lead Classic sealed
type
(Sealed lead)
Wet lead
Opened type bat
free electrolyte
Lithium
(LiFePO4) with BMS
(***)
Custom
(*)
Output voltage with 10% of the rated current and a tolerance of +/- 1%.
(
)
**
REFRESH is not advised for certain types of AGM batteries
(***)
Battery Management System
3.4.1.2 Boost and Refresh mode
- The BOOST function enables faster recharging of the batteries.
- The REFRESH function applies a voltage step periodically to maintain and equalize the battery, thus
preventing sulphation. (see chapter 3.6).
Floating voltage
13.8V
27.6V
41.1V
55.2V
13.4V
26.8V
40.2V
53.6V
13.8V
27.6V
41.1V
55.2V
BOOST mode
FACTORY SETTING (by default)
Boost voltage
14.4V
28.8V
43.2V
57.6V
14.1V
28.2V
42.3V
56.4V
14.4V
28.8V
43.2V
57.6V
Via Bluetooth
REFRESH mode
OFF
ON
OFF
ON
Maximum
Maximum
duration of
duration of
BOOST at
ABSOPTION at
+/- 5% T
+/- 5% T
BOOST
2H
4H
2H
4H
6H
1H
OFF
OFF
ON
ON
ABS
9