3.4.4.7 CANBUS protocol
This function enables to change CAN protocol
CRISTEC
MULTIBLOC
PBUS
3.4.4.8 Starting delay
You can set this value to start the charger after the starting phase of an input supply.
Starting delay (in seconds)
0 s
0.5 s
1 s
2 s
3.4.4.9 CANBUS
Communication
Bus-CAN documentation (hardware and software
specifications) is available on request from CRISTEC.
To enable communication between several devices,
have a unique identifier (ID). This ID must be selected using the 4 microswitches (1,2,3,4) available on the
connection side.
Within a single CAN network, 4 sub-networks (A, B, C, D) can be defined.
This means that only the 4 sub-network entities can communicate with each other. For example: Master A
and Slaves A1, A2 & A3.
Switches settings
1
2
3
0
0
0
1
0
0
0
1
0
1
0
0
Factory settings (by default):
0
0
1
1
0
1
0
1
1
1
1
1
0
0
0
1
0
0
0
1
0
1
1
0
0
0
1
1
0
1
0
1
1
1
1
1
CAN-Bus protocol
Protocol Cristec
Protocol Scheiber
Protocol Philippi
3 s
6 s
12 s
24 s
Master/Slave
ID
4
N°
0
0
0
1
0
2
0
3
4
0
0
5
0
6
0
7
1
8
1
9
1
10
1
11
1
12
1
13
1
14
1
15
Dip-switches:
(1, 2, 3 et 4)
function
Master A
Master B
Master C
Master D
Slave A1
Slave B1
Slave C1
Slave D1
Slave A2
Slave B2
Slave C2
Slave D2
Slave A3
Slave B3
Slave C3
Slave D3
each entity must
Sub-network
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
15